User Manual Owner's manual

Publication 1746-UM007C-EN-P - July 2004
5-4 Channel Configuration, Data, and Status
Bit(s) Define To Select Make these bit settings in the Channel Configuration Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0-3 Input type Thermocouple Type J 0 0 0 0
Thermocouple Type K 0 0 0 1
Thermocouple Type T 0 0 1 0
Thermocouple Type E 0 0 1 1
Thermocouple Type R 0 1 0 0
Thermocouple Type S 0 1 0 1
Thermocouple Type B 0 1 1 0
Thermocouple Type N 0 1 1 1
50mV 1000
100mV 1001
Invalid 1010
Invalid 1011
Invalid 1100
Invalid 1101
Invalid 1110
CJC temperature 1 1 1 1
4 and 5 Data format
Engineering units x 1
(2)
00
Engineering units x 10
(2)
01
Scaled–for–PID 1 0
Proportional Counts 1 1
6 and 7 Open circuit Zero 0 0
Upscale 0 1
Downscale 1 0
Invalid 1 1
8
Temp
(1)
Degrees C 0
Degrees F 1
9 and 10 Channel filter
frequency
10 Hz 0 0
50 Hz 0 1
60 Hz 1 0
250 Hz 1 1
11 Channel
enable
Channel Disabled 0
Channel Enabled 1
12-15 Unused Unused 0 0 0 0
(1) When millivolt input type is selected, the bit setting for temperature units is ignored.
(2) For engineering units x1, values are expressed in 0.1 degrees or 0.01 mV. For engineering units x10, values are expressed in 1.0 degrees or 0.1 mV.