User Manual Owner's manual

Publication 1746-UM007C-EN-P - July 2004
Quick Start for Experienced Users 2-5
6. Determine the operating parameters. Reference
Determine the operating parameters for channel 0. This example shows the channel 0
configuration word defined with all defaults (0) except for channel enable (bit 11). The
addressing reflects the location of the module as slot 1.
Chapter 4
(Preliminary
Operating
Considerations)
Chapter 5
(Channel
Configuration,
Data, and
Status)
Appendix B
(NT4
Configuration
Worksheet)
O:1.1
Channel 1 Configuration W
ord
Channel 2 Configuration W
ord
Channel 3 Configuration W
ord
W
ords 4 7
(not defined)
Output Image
SLC 500 Controller
Data Files
Bit
15
Bit 0
W
ord 1
W
ord 2
W
ord 3
Address
O:1.0
Input Image
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Channel 0 Configuration Word
W
ord 0
W
ord 7
Input
Type
Data Format
Open Circuit
T
emperature Units
Filter Frequency
Channel Enable
Unused
(8 words)
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
Default Setting
New Setting
Set this bit (11) to enable channel. Address = O:1.0/11.
Type J Thermocouple
Engineering Units x 1
Data Word = 0 If Open Circuit
Degrees Celsius
10 Hz. Filter Frequency
Channel Disabled
O:1.2
O:1.3
O:1.7
_