1-6 Overview
Input Circuit Block Diagram
Input Circuit Block Diagram
Digital
Value
User-Selected
Filter Frequency
Digital
Filter
Analog to
Digital
Convertor
Multiplexer
Open Circuit
Detection
+
-
Shield
+
-
+
-
Shield
+
-
Shield
+
-
+
-
CJCA
Sensor
CJCB Sensor
Terminal Block Module Circuitry
Chassis Ground
(internally connected)
Channel
1
+
-
Shield
user supplied
jumper
grounded
thermocouple
Channel
2
within
2V*
grounded
thermocouple
Channel
3
Channel 0
within
2V*
grounded
thermocouple
ungrounded
thermocouple
Analog
Common
*See Important note below.
IMPORTANT
When using multiple grounded and/or exposed
thermocouples that are touching on electrically
conductive material with Series B or higher
1746-NT4, the ground potential between any two
channels cannot exceed 2 volts.