User Manual Owner's manual
Publication 1746-UM007C-EN-P - July 2004
Configuring the 1746-NT4 Module with RSLogix 500 E-3
The dialog box allows you to access the parameters for all channels.
Each tab has an identical menu with the parameters shown.
The following list provides the options for a parameter.
Parameter Description
Channel Enabled Controls bit 11 of the configuration file and sets whether
the channel is being used.
Input Type Sets bits 0-3 and sets the type of thermocouple being
used.
Temperature Units Set bit 8 for temperature (celsius or fahrenheit)
Filter Frequency Sets bits 9-10 and determines the frequency of the
channel filter.
Broken Input Sets bits 6-7 and determines how to handle an open
circuit condition.
Data Format Sets bits 4-5 and determines the scale of the data.