Table 4.25 Channel 0 through 7 Status Word (I:e.8 through I:e.15) - Bit Definitions
Bit(s) Define These bit settings Indicate this
1514131211109876543210
0 through 3 Input type
status
0000100 Pt RTD (385)
0001200 Pt RTD (385)
0010500 Pt RTD (385)
00111000 Pt RTD (385)
0100100 Pt RTD (3916)
0101200 Pt RTD (3916)
0110500 Pt RTD (3916)
01111000 Pt RTD (3916)
1000
10
Cu RTD (426)
(1)
1001
120
Ni RTD (618)
(2)
1010120 Ni RTD (672)
1011604 NiFe RTD (518)
1100150 Resistance Input
1101500 Resistance Input
11101000 Resistance Input
11113000 Resistance Input
4 through 5 Data format
status
00
Engineering units x 1
(3)
01
Engineering units x 10
(4)
10 Scaled-for-PID
11 Proportional Counts
6 through 7 Broken input
status
00 Set to Zero
01 Set to Upscale
10 Set to Downscale
11 Not used
8 Temperature
units status
0
Degrees C
(5)
1
Degrees F
(5)
9 through 10 Filter frequency
status
00 28 Hz
01 50/60 Hz
10 800 Hz
11 6400 Hz
11 Channel enable
status
0 Channel Disabled
1 Channel Enabled
12 Calibration Error
0 OK
1 Error
13 Broken input
0 OK
1 Error
14 Out-of-range
error status
0 OK
1 Error
15 Configuration
Error
0
OK
1
Error
(1) Actual value at 0°C is 9.042 per SAMA standard RC21-4-1966.
(2) Actual value at 0°C is 100 per DIN standard.
(3) Values are in 0.1 degree /step or 0.1/step for all resistance input types, except 150. For the 150 resistance input type, the values are in 0.01/step.
(4) Values are in 1 degree /step or 1/step for all resistance input types, except 150. For the 150 resistance input type, the values are in 0.1/step.
(5) This bit is cleared (0) when a resistance device, such as a potentiometer, is selected.