Owner manual

16 SLC 500™ Analog Input Modules
Publication 1746-IN001B-US-P
Physical Specifications
Environmental Specifications
Description Specification
LED Indicators 5 green status indicators
one for each group of 4 channels and one for module status
Module ID Code Class 1 Class 3
NI16V 3505 10406
NI16I 3504 10403
Recommended Cable Belden #8761 or equivalent
Maximum Wire Size Two 14 AWG wires per terminal
Maximum Cable
Impedance
NI16V Voltage Source (with less than 10 impedance): 1250
maximum loop impedance, for <1LSB error
NI16I Current Source (transmitter properly wired to its power supply):
249 maximum loop impedance, to meet common-mode
voltage requirements
Terminal Block Removable, Allen-Bradley spare part
Catalog Number 1746-RT25G
Allen-Bradley Prewired
Cables
1492-ACAB005A46, 0.5m (1.6 ft.)
1492-ACAB010A46, 1.0 m (3.3 ft.)
1492-ACAB025A46, 2.5 m (8.2 ft.)
1492-ACAB050A46, 5.0 m (16.4 ft.)
Allen-Bradley User Terminal
Blocks
1492-AIFM8-3
1492-AIFM16-F-3
Description Specification
Operating Temperature +0°C to +60°C (+32°F to +140°F)
Storage Temperature
-40°C to
+85°C (-40°F to +185°F)
Relative Humidity 5% to 95% (without condensation)
Agency Certification UL listed
C-UL approved
CE compliant for all applicable directives
Hazardous Environment
Classification
Class I Division 2 Hazardous Environment Groups A, B, C, D
@JO#VTQQE@JO#VTQQE ".".