(1) Refer to the thermocouple manufacturer for the correct extension wire.
Environmental
Specifications
Input Specifications
Max wire size Two 1.6 mm (14 AWG) wires per terminal
Max cable impedance 150 Ω max loop impedance, for < 1LSB error
Terminal strip Removable, catalog number 1746-RT32
Attribute Value
Attribute Value
Temperature, operating 0… 60 °C (32…140 °F)
Temperature, storage -40…85 °C (-40…185 °F)
Relative humidity 5…95% (without condensation)
Agency certification
(when product is marked)
CSA certified
CSA Class I, Division 2, Groups A, B, C, D certified
Hazardous Locations
UL listed
CE marked for all applicable directives
Attribute Value
Type of input (selectable)
Thermocouple Type C 0…2317 °C (32…4201 °F)
Thermocouple Type D 0…2317 °C (32…4201 °F)
Thermocouple Type J -210…760 °C (-346…1400 °F)
Thermocouple Type K -270…1370 °C (-454…2498 °F)
Thermocouple Type T -270…400 °C (-454…752 °F)
Thermocouple Type E -270…1000 °C (-454…1832 °F)
Thermocouple Type R 0…1768 °C (32…3214 °F)
Thermocouple Type S 0…1768 °C (32…3214 °F)
Thermocouple Type B 300…1820 °C (572…3308 °F)
Thermocouple Type N 0…1300 °C (32…2372 °F)
1.6 mm (14 AWG)
Millivolt (–50…50 mV dc)
Millivolt (–100…100 mV dc)
Thermocouple linearization IPTS–68 standard, NBS MN–125, NBS MN–161
Cold junction compensation Accuracy ±1.5 °C (34.7 °F), 0 … 70 °C (32…158 °F)
Input impedance Greater than 10 MΩ