User Manual Owner's manual

Publication 1746-UM614B-EN-P - September 2007
74 Application Programming Examples
Channel Configuration
All channels are configured for:
display temperature to tenths of a degree.
zero data word in the event of an open-circuit.
Configuration setup for ambient thermocouple:
channel 0.
type T thermocouple.
Configuration setup for bath thermocouple:
channel 1.
type J thermocouple.
Configuration setup for steam thermocouple:
channel 2.
type K thermocouple.
Configuration setup for chilled H
2
O thermocouple:
channel 3.
type J thermocouple.
Configuration setup for cabinet temperature:
channel 0.
CJC temperature.
Configuration Word
12131415 8 674 123
0010000 x 00 00 0010
00
10000 x 00 00 0000
00
10000 x 00 00 0001
00
10000 x 00 00 0000
Channel 0
Channel 1
Channel 2
Channel 3
(Ambient)
(Bath)
(Steam)
(Chilled H2O)
0010000 x 00 00 1111
Channel 3 (Cabinet)
910
50
11
Not Used Channel
Enable
0 = Disable
1 = Enable
Not
Used
Temp
Units
0 = °C
1 = °F
Response to
Open-circuit
0 0 = zero
0 1 = FS
1 0 = LS
Data
Format
0 0 = EU x1
0 1 = EU x10
1 0 = Scaled PID
1 1 = Prop Counts
Type
of Input
0 0 0 0 = Type J
0 0 0 1 = Type K
0 0 1 0 = Type T
0 0 1 1 = Type E
0 1 0 0 = Type R
0 1 0 1 = Type S
0 1 1 0 = Type B
0 1 1 1 = Type N
1 0 0 0 = 0…100 mV
1 0 0 1 = ±100
1 0 1 0 = Type C
1 0 1 1 = Type D
1 1 1 1 = CJC Temp