User Manual Owner's manual

Publication 1746-UM614B-EN-P - September 2007
26 Install and Wire the Module
Considerations for a Modular System
Place your module in any slot of an SLC 500 modular, or modular
expansion chassis, except for the leftmost slot (slot 0) reserved for the
SLC processor or adapter modules.
Considerations for a Fixed Controller
The power supply in the two slot SLC 500 fixed I/O chassis (1746-A2)
can support only specific combinations of modules.
Refer to the table at the left or to the Chart Method below to
determine whether the power supply can support the pair of modules.
Chart Method
Follow these steps to use the chart to determine a valid pair of
modules.
1. For both modules, add the current rating at 5V dc and again at
24V dc.
2. On the chart, draw a horizontal line for the total 5V dc current
rating.
3. On the chart, draw a vertical line for the total 24V dc current
rating.
4. Observe the intersection; if within the chart boundary, the pair
is OK.
Fixed Controller Compatibility
Module
INT4 5V dc
A
24V dc
A
IA4
Yes 0.035
IA8
Yes 0.050
IA16
Yes 0.085
IM4
Yes 0.035
IM8
Yes 0.050
IM16
Yes 0.085
OA8
Yes 0.185
OA16
Yes 0.370
IB8
Yes 0.050
IB16
Yes 0.085
IV8
Yes 0.050
IV16
Yes 0.085
IG16
Yes 0.140
OV8
Yes 0.135
OV16
Yes 0.270
OB8
Yes 0.135
OG16
Yes 0.180
OW4
Yes 0.045 0.045
OW8
Yes 0.085 0.090
OW16
0.170 0.180
IO4
Yes 0.030 0.025
I08
Yes 0.060 0.045
IO12
Yes 0.090 0.070
NI4
Yes 0.025 0.085
NIO4I
0.055 0.145
NIO4V
0.055 0.115
DCM
0.360
HS
Yes 0.300
OB16
Yes 0.280
IN16
Yes 0.085
INT4
Yes 0.110 0.085
BAS
Yes 0.150 0.040
OB32
0.452
OV32
0.452
IV32
Yes 0.106
IB32
Yes 0.106
OX8
Yes 0.085 0.090
NO4I
0.055 0.195
NO4V
0.055 0.145
ITB16
Yes 0.085
ITV16
Yes 0.085
KE
Yes 0.150 0.040
KEn
0.150 0.145
OBP16
Yes 0.250
NT4
Yes 0.060 0.040
FIO4I
0.055 0.150
FIO4V
0.055 0.120