An example of Sequencer Mode with a linear counter is shown below.
Sequencer Mode with Linear Counter
Output 0
10,000
20,000
30,000
Reset Value
0
12345
0
12 3 45
1201
12 312
25,000
15,000
5,000
Current Sequencer Step
Next Sequencer Step
Reset Condition
Sequencer Reset (M0:e.1/0)
Output 1
Output 2
Output 3
Accumulated
Count
Number Desired Trigger Preset Value
Outputs
(1)
(1) Bits 0-3 are physical outputs, bits 4-7 are soft outputs.
76543210
Initial Outputs 00000000
1 10,000 9,999 00000001
2 25,000 24,999 00000010
3 15,000 15,001 00000011
4 10,000 10,001 00000100
5 20,000 19,999 00001101
IMPORTANT
Resetting the counter does not reset the sequencer,
unless the Sequencer Reset bit (M0:e.1/0) is set to 1