User guide
Publication 1746-UM006B-EN-P - August 2005
Range/Rate Mode Configuration Worksheets D-5
Input Data File Worksheets
Shown below is the Range/Rate Mode Configuration Worksheet for
the Input File.
Status Word (page 4-16)
Accumulated Count, Rate Period Count, and Rate Measurement (decimal)
(page 4-20)
Output Status and Configuration Error Code (page 4-21)
Status Word
I:e.0
Bit Number (decimal)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
R
0 = No configuration error
1 = Invalid configuration data
0 = No overflow
1 = Overflow
0 = Invalid rate
1 = Rate valid
0 = No overflow
1 = Overflow
0 = No error detected
1 = Error detected
0 = No error detected
1 = Overflow/Underflow
00 = Stopped
01 = Running
10 = Undefined
11 = Hold
0 = False Reset Mode
1 = T
rue Reset Mode
RRR RR
R
= Reserved
0 = Nonzero Rate Period count
1 = Rate Period Count is 0
Overflow/Underflow (page 4-20)
Configuration Error (page 4-19)
Rate Counter Overflow (page 4-17)
Zero Rate Period Count (page 4-16
)
Pulse Counter State (page 4-20)
Reset Input (page 4-19)
Critical Error (page 4-18)
Rate Measurement Overflow (page 4-18)
Rate Valid (page 4-17)
I:e.1
I:e.2
I:e.3
Accumulated Count
Rate Period Count
Rate Measurement (Hz)
I:e.4
7654 3210Bit Number (decimal) 15 14 13 12 11 10 9 8
Output
Number
765 4321 0
Output Status and Configuration Error Code
0000 = No error
0001 = not defined
0010 = Max Count equals 0 (ring)
0011 = Invalid Operating Mode
0100 = Invalid Input Type
0101 = Static Parameter Changed
01
10 = Ranges Active equals 0
011
1 = Rate Period equals 0
1000 = Linear Counter Reset V
alue out of range
1001 = Sequencer Preset > Maximum Count
Configuration Error Code
RR RR
0 = output OFF
1 = output ON
Output Status
Outputs 0 thru 3 relate to Physical Outputs
Outputs 4 thru 7 relate to Soft Outputs