User guide

Publication 1746-UM006B-EN-P - August 2005
Application Examples 6-23
Accumulated Count, Rate Period Count, and Rate Measurement (decimal)
Output Status and Configuration Error Code
Ranges Active
Module Setup Information
Module ID Code = 12705 (8 Input and 1 Output word) 42 M0 File
words
File size - 42 word integer file, 42 word M0 File
I:e.1
I:e.2
I:e.3
Accumulated Count
Rate Period Count
Rate Measurement (Hz)
689
0
0
0
5
7
5
9
6
1
I:e.4
7654 3210Bit Number (decimal) 15 14 13 12 11 10 9 8
Output
Number
765 4321 0
Output Status and Configuration Error Code
0000 = No error
0001 = not defined
0010 = Max Count equals 0 (ring)
0011 = Invalid Operating Mode
0100 = Invalid Input Type
0101 = Static Parameter Changed
01
10 = Ranges Active equals 0
011
1 = Rate Period equals 0
1000 = Linear Counter Reset V
alue out of range
1001 = Sequencer Preset > Maximum Count
Configuration Error Code
RR RR
0 = Output OFF
1 = Output ON
Output Status
Outputs 0 thru 3 relate to Physical Outputs
Outputs 4 thru 7 relate to Soft Outputs
000000010000
Range
Number
12 11 10 9 8
I:e.6
765 4321 0Bit Number (decimal) 15 14 13 12 11 10 9 8
Ranges Active
Ranges Active
1 = Range Active
RRRR
7654 321
0000
00
0000000
00
00
1