User guide
Publication 1746-UM006B-EN-P - August 2005
Configuration and Programming 4-43
I:e.3 Rate Measurement (Hz)
This word indicates the current rate at which the count is being
received (in Hz). This value is updated after every Rate Period.
This input value is active in all modes. When the module is used with
encoders and configured for x2 or x4 input types, the calculated value
will be scaled down by a factor or two or four respectively.
I:e.4 Output Status, Configuration Error Code
I:e.4 Bits 0 through 7 - Configuration Error Code
Bit Number (decimal) 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Rate Measurement Word 3
I:e.3
Bit Number (decimal) 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Output Status and Configuration Error Code, Word 4
I:e.4
Physical
Outputs 0–3
Configuration Error Code
Soft Outputs 4–7
Configuration
Error Code
Reason Critical
Error
Action
Hex Binary
01 0000 0001 not defined -
reconfigure
(1)
(1) The Function Control bit must be reset to 0, the parameter must be changed, and the Function Control bit is
then set to 1
.
02 0000 0010 max count = 0 (ring) yes
reconfigure
(1)
03 0000 0011 invalid operating mode yes
reconfigure
(1)
04 0000 0100 invalid input type yes
reconfigure
(1)
05 0000 0101 static parameter changed yes
reconfigure
(1)
06 0000 0110 ranges active = 0 no change parameter
07 0000 0111 rate period = 0 no change parameter
08 0000 1000 linear counter reset value out of range no change parameter
09 0000 1001 sequencer preset > max. count no change parameter