Installing and Wiring 2-9
7. At the source-end of cables from mV devices (See Figure 2.3
and Figure 2.4):
remove the drain wire and foil shield
apply shrink wrap as an option
connect to mV devices keeping the leads short
Figure 2.4 Cable Preparation to Minimize Electrical Noise Interference
Wires
3/8”
Make
unshielded
wires as
short as
possible.
Limit braid length to 12” or
less. Solder braid to lug on
bottom row of I/O chassis
bolts.
Connect I/O
chassis bolt to
earth ground
Solder drain wires to
braid at casing.
Make unshielded wires
as short as possible.
3/8”
Signal
Wires
Terminal
Block
Chnl 0
Chnl 1
Chnl 2
Chnl 3
n/c
Cables
IMPORTANT
If noise persists, try grounding the opposite end of
the cable. Ground one end only.