Publication 1746-IN014B-EN-P - January 2001
Digital Output Type Open Collector
Maximum OFF State Voltage 30Vdc
Isolation from PLC backplane Tested to 500Vdc for 60 sec or equivalent
Output Conductors: Wire size Belden 8761 or equivalent
22-14 AWG stranded maximum
3/64 inch insulation maximum
Wire Category 2
(2)
Environmental
(1)
Power requirement 5 Watts (1A @ +5Vdc)
Operating (ambient) temperature 0 to 60°C
Storage temperature -40 to +85°C
Relative humidity 5 to 95% (non-condensation)
Agency Certifications
When product is marked:
(1)
This product must be mounted within a suitable system enclosure to prevent personal injury resulting from
accessibility to live parts. The interior of this enclosure must be accessible only by the use of a tool. This
industrial control equipment is intended to operate in a Pollution Degree 2 environment, in overvoltage
category II applications, (as defined in IEC publication 664A) at altitudes up to 2000 meters without
derating.
(2)
See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Listed Industrial Control Equipment
N223
Certified Process Control Equipment
Certified for use in Class I, Division 2, Groups A, B, C, D or
nonhazardous locations
Marked for all applicable acts
Marked for all applicable directives