Manual

Publication 1746-UM004B-EN-P - December 2005
1-2 Module and Development Software Overview
BASIC and BASIC-T
Modules
The modules are single-slot modules that reside in a SLC 500 fixed or
modular controller chassis. Use the module as
:
a foreign device interface.
an operator interface.
Figure 1.1 Module with Door Open
Hardware Features
The module provides the following hardware features.
24 KB of battery backed RAM for storage of user programs and
data
Capacitive backup of RAM during battery change
Socket for a standard 1747-M1, M2, M3, or M4 memory module
(1746-BAS module) for nonvolatile storage of user programs
Socket for a 1771-DBMEM1 or -DBMEM2 memory module
(1746-BAS-T module) for nonvolatile storage of user programs
Battery-backed, 24-hour clock/calendar
Free-running clock with 5 ms resolution
Two isolated 9-pin D-shell serial ports (PRT1 and PRT2) that
provide RS-232/423, RS-422, and RS-485 communication with
I/O devices
One PRT2 port provides DF1 full-duplex or half-duplex slave
protocol for SCADA applications
One RJ-45 port (DH485) that provides communication over the
DH485 network
Multiple LED indicators for operator interface