Installation Instructions ArmorPoint 24V dc Output Modules, Series A Catalog Numbers 1738-OB8EM23, 1738-OB8EM12, 1738-OB8EM8, 1738-OB4EM12, 1738-OB4EM8, 1738-OB2EM12, 1738-OB2EPM12, 1738-OV4EM12 The ArmorPoint I/O family consists of modular I/O modules. The sealed IP67 housing of these modules requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) I/O connectors are sealed M8 (pico) or M12 (micro) or M23 styles.
ArmorPoint 24V dc Output Modules, Series A . Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
ArmorPoint 24V dc Output Modules, Series A ATTENTION 3 Environment and Enclosure This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
ArmorPoint 24V dc Output Modules, Series A Preventing Electrostatic Discharge ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment.
ArmorPoint 24V dc Output Modules, Series A 5 Install the mounting base as follows: 1. Lay out the required points as shown above in the drilling dimensions drawing. 2. Drill the necessary holes for #8 (M4) machine or self-tapping screws. 3. Mount the base using #8 (M4) screws. 4. Ground the system using the ground lug connection. The ground lug connection is also a mounting hole.
ArmorPoint 24V dc Output Modules, Series A Install the ArmorPoint Digital Output Module To install the ArmorPoint digital output module, proceed as follows. 1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 1 aligns with the notch in the base. 2. Position the module vertically above the mounting base. The module bridges two bases. Module bridges two bases. 1738-OB8EM12/A 24V dc Out 0 2 1 3 MOD NET 0 1 2 3 4 6 5 7 4 5 6 7 43771 3.
ArmorPoint 24V dc Output Modules, Series A Wire the Modules 7 Following are wiring instructions for the ArmorPoint digital output modules.
ArmorPoint 24V dc Output Modules, Series A 1738-OB8EM23 1 (view into connector) Pin 1 -Output 0 Pin 2 -Output 1 Pin 3 -Output 2 Pin 4 -Output 3 Pin 5 -Output 4 Pin 6 -Output 5 8 9 7 2 10 12 6 3 11 4 5 43681 ATTENTION Communicate with Your Module Pin 7 - Output 6 Pin 8 - Output 7 Pin 9 - Return (Com) Pin 10 - Return (Com) Pin 11 - 24V dc Pin 12 - Chassis Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements.
ArmorPoint 24V dc Output Modules, Series A 9 1738-OB4EM12, 1738-OB4EM8, 1738-OV4EM12 Message size: 1 Byte 7 6 5 4 3 2 1 0 Produces (scanner Rx) Not Used Ch3 Ch2 Ch1 Ch0 Channel status Consumes (scanner Tx) Not Used Ch3 Ch2 Ch1 Ch0 Output state Where: Channel status 0 = no error, 1 = error; Output state 0 = off, 1 = on 1738-OB8EM23, 1738-OB8EM12, 1738-OB8EM8 Message size: 1 Byte 7 6 5 4 3 2 1 0 Produces (scanner Rx) Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0 Channel status Con
ArmorPoint 24V dc Output Modules, Series A Troubleshoot with the Indicators 1738-OB8EM12 1738-OB8EM12/A 24V dc Out 0 2 1 3 Module Status Indicator Network Status Indicator MOD NET 0 1 2 I/O Status Indicators 3 4 6 5 7 4 5 6 7 43676 Indication Probable Cause Module Status Off No power applied to device Green Device operating normally Flashing Green Device needs commissioning due to missing, incomplete, or incorrect configuration Flashing Red Recoverable fault Red Unrecoverable
ArmorPoint 24V dc Output Modules, Series A Indication 11 Probable Cause I/O Status Off Output is inactive. Yellow Output is active and under control. Flashing Red Open circuit detection. No load. (Off-State only) Red Short circuit detected. (On-State only) Specifications ArmorPoint Digital Output Modules Number of Outputs Voltage Drop, On-state Output, Max. Voltage, External DC Power Supply, Range Voltage, External DC Power Supply, Nom. Voltage, Off-state Output, Max.
ArmorPoint 24V dc Output Modules, Series A General Specifications (cont) LED Indicators Output Delay Time, OFF to ON, Max.1 Output Delay Time, ON to OFF, Max.1 Output Point Density PointBus Current, Max. Power Dissipation, Max. Thermal Dissipation, Max.
ArmorPoint 24V dc Output Modules, Series A General Specifications (cont) Enclosure Type Rating Mounting Base Screw Torque Conductor Category2 13 Meets IP65/66/67 (when marked) #8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel 1 - on signal ports c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada CE European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab.
Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.