Installation Instructions ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Catalog number 1738-VHSC24M23 The ArmorPOINT® I/O family (Bulletin 1738) consists of modular I/O modules. The sealed IP67 housing of these modules requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) The I/O connector is sealed M23 style. The mounting base ships with the module. The 1738-VHSC24M23 module is shown below.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A ATTENTION 3 Environment and Enclosure This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Mount the I/O Base To mount the ArmorPOINT I/O base on a wall or panel, use the screw holes provided in the ArmorPOINT base. IMPORTANT The ArmorPOINT I/O module must be mounted on a grounded metal mounting plate or other conductive surface. A mounting illustration for the ArmorPOINT base with an adapter is shown below. Adapter 1.9 in. 47.2 mm 2.0 in. 50 mm 0.87 in. 22 mm 2.0 in. 50 mm 0.87 in. 22 mm 2.0 in. 50 mm 4.02 in. 102 mm 1.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A 5 Install the mounting base as follows: 1. Lay out the required points as shown above in the drilling dimension drawing. 2. Drill the necessary holes for #8 (M4) machine or self-tapping screws. 3. Mount the base using #8 (M4) screws. 4. Ground the system using the ground lug connection. (The ground lug connection is also a mounting hole.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Install the ArmorPOINT Very High Speed Counter Module To install the ArmorPOINT Very High Speed Counter module, proceed as follows. 1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 2 aligns with the notch in the base. 2. Position the module vertically above the mounting base. The module will bridge two bases. Module will bridge two bases.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Wire the Very High Speed Counter Module 7 Following are wiring instructions for the ArmorPOINT Very High Speed Counter module.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Communicate With Your Module I/O messages are sent to (consumed) and received from (produced) the ArmorPOINT I/O modules. These messages are mapped into the processor’s memory. This ArmorPOINT I/O input/output module produces 6 or 10 bytes of input data (scanner Rx - status). It consumes 2 or 4 bytes of I/O data (scanner Tx). See the 1738 ArmorPOINT adapter User Manual, publication 1734-UM016, for specific parameter information.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A 9 Note that when a configuration is sent to the module, it is checked for consistency before being applied. If an error is found in the configuration, the PE bit is asserted and the module retains its previous configuration. Monitor this PE bit with your user program to isolate any problems an improperly configured module may have.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Configure the Very High Speed Counter Module Parameter Publication 1738-IN011B-EN-E - August 2013 Set/Get Description Bytes 1 Set/Get Counter Configuration (see page 11) 1 2 Set/Get Filter Selection (see page 12) 1 3 Set/Get Decimal Position 1 4 Set/Get Active Output Assembly 1 5 Set/Get Time Base Value/PWM Period 2 6 Set/Get Gate Interval 1 7 Set/Get Channel Scalar (see page 12) 1 8 Set/Get Output 0 Ties 1
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A 11 Counter Configuration 07 06 05 04 03 02 01 00 ZI MD CF Counter 0 0 0 0 0 Counter 0 0 0 1 Encoder X1 0 0 1 0 Encoder X2 0 0 1 1 PWM 0 1 0 0 Encoder X4 0 1 0 1 Period/Rate 0 1 1 0 Continuous/Rate 0 1 1 1 Rate Measurement 1 0 0 0 Pulse Generator 0 0 0 Store Count Disabled 0 0 1 Mode 1 - store/continue 0 1 0 Mode 2 - store/wait/resume 0 1 1 Mode 3 - store, reset/wait/start 1 0 0 Mo
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Filter Selection 07 06 05 04 0 ZF BF AF 03 02 01 00 FS 0 0 0 0 No Filter 0 0 0 1 50kHz (10μs + 0μs/-1.6μs) 0 0 1 0 5kHz (100μs + 0μs/-13.2μs) 0 1 0 0 500Hz (1.0ms + 0ms/-125μs) 1 0 0 0 50Hz (10ms + 0ms/-1.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A 13 Assemblies The Very High Speed Counter Module uses several words to communicate real time input and output data as well as non-real time module information (that is, description, revision, and so on) and configuration. The following table shows the words which can be exchanged. Data may be read (get) or written (set) using an explicit message.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Instances (Dec/Hex) #123 (0x7b) Publication 1738-IN011B-EN-E - August 2013 Services Field Set/Get Bytes OFF Value #2 4 ON Value # 3 4 OFF Value #3 4 ON Value # 4 4 OFF Value #4 4 PWM Safe State Value 2 Counter Control SSV 1 Output Control SSV 1 Counter Configuration 1 Filter Selection 1 Decimal Position 1 Active Output Assembly 1 Time Base or PWM Period 2 Gate Interval 1 Scalar 1 Output 0 Ties 1 Output 1 T
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Troubleshoot with the Indicators 15 1738-VHSC24M23 1738-VHSC24M23/A 24V dc In Module Status Indicators Network Status Indicators MOD NET A B I/O Status Indicators Z 0 1 43803 Indication Probable Cause Module Status Off No power applied to device Green Device operating normally Flashing Green Device needs commissioning due to missing, incomplete, or incorrect configuration Flashing Red Recoverable fault Red Unrecoverable fault -
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Indication Probable Cause Network Status Off Device is not online: – Device has not completed dup_MAC-id test. – Device not powered. Check module status indicator. Flashing Green Device is online but has no connections in the established state. Green Device is online and has connections in the established state. Flashing Red One or more I/O connections in timed-out state. Red Critical link failure – failed communication device.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A Specifications ArmorPOINT 1738-VHSC24M23 Module Input Specifications Inputs per Module Input Voltage Input Current Input OFF-State Voltage Input OFF-State Current, max Input ON-State Voltage Input ON-State Current Maximum ON-State Voltage Input Filter Selections Maximum Input Frequency Output Specifications Outputs per Module Output Control Output Supply Voltage Range OFF-State Leakage Current ON-State Voltage Drop ON-State Current, max Short Ci
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A General Specifications (continued) Dimensions (HxWxD) Temperature, Operating Temperature, Nonoperating Relative Humidity Shock, Operating Shock, Nonoperating Vibration ESD Immunity Radiated RF Immunity EFT/B Immunity Surge Transient Immunity Conducted RF Immunity Emissions Enclosure Type Rating Mounting Base Screw Torque Weight (approx.) Wiring Category2 Publication 1738-IN011B-EN-E - August 2013 31.75 x 66.80 x 107.95 mm (1.25 x 2.
ArmorPOINT 24V DC Very High Speed Counter Modules, Series A General Specifications (continued) Certifications: (when product is marked) 19 c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada CE3 European Union 2004/108/EC EMC Directive, compliant with: EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) EN 61326-1; Meas./Control/Lab.
Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using our products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.