Installation Instructions ArmorPoint Relay Output Modules, Series A (Cat. No. 1738-OW4M12 and -OW4M12AC) The ArmorPoint I/O family (Cat. no. 1738) consists of modular I/O modules. The sealed IP67 housing of these modules requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) I/O connectors are sealed M12 with either DC or AC keyed (micro) styles. The mounting base ships with the module.
ArmorPoint Relay Output Modules, Series A Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices.
ArmorPoint Relay Output Modules, Series A ATTENTION 3 Environment and Enclosure This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
ArmorPoint Relay Output Modules, Series A ATTENTION Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment.
ArmorPoint Relay Output Modules, Series A 5 3. Mount the base using #8 (M4) screws. 4. Ground the system using the ground lug connection. (The ground lug connection is also a mounting hole.) Mounting base KeyswitchSet to position 7 for the 1738 Relay output modules Ground lug connection 43675 Latching mechanism Install the ArmorPoint Relay Output Module To install the ArmorPoint relay output module, proceed as follows. 1.
ArmorPoint Relay Output Modules, Series A 3. Push the module down until it engages the latching mechanism. You will hear a clicking sound when the module is properly engaged. The locking mechanism will lock the module to the base. Remove the ArmorPoint Relay Output Module From the Mounting Base To remove the module from the mounting base: 1. Put a flat blade screwdriver into the slot of the orange latching mechanism. 2. Push the screwdriver toward the I/O module to disengage the latch.
ArmorPoint Relay Output Modules, Series A Wire the Relay Output Modules 7 Following are wiring instructions for the ArmorPoint relay output modules.
ArmorPoint Relay Output Modules, Series A Communicate With Your Module I/O messages are sent to (consumed) and received from (produced) the ArmorPoint I/O module. These messages are mapped into the processor’s memory. The ArmorPoint I/O relay output module consumes 1 byte of output data (scanner Tx - status). It does not produce data (scanner Rx).
ArmorPoint Relay Output Modules, Series A Troubleshoot with the Indicators 9 1738-OW4M12 1738-OW4M12/A Form A Isolated Relay Out 1 0 Module Status Indicators Network Status Indicators MOD NET 2 3 0 1 I/O Status Indicators 2 3 43717 Indication Probable Cause Module Status Off No power applied to device Green Device operating normally Flashing Green Device needs commissioning due to missing, incomplete, or incorrect configuration Flashing Red Recoverable fault Red Unrecoverable fault -
ArmorPoint Relay Output Modules, Series A Indication Probable Cause I/O Status Specifications Off Output is inactive Yellow Output is active and under control Following are specifications for the 1738 ArmorPoint relay output modules. ArmorPoint Relay Output Modules Outputs per Module Output Voltage Range (load dependent) 4 Form A isolated (normally open) electromechanical relays 1738-OW4M12 only - 5-28.8V dc @ 2.0A resistive 1738-OW4M12AC only 5-28.8V dc @ 2.0A resistive 48V dc @ 0.
ArmorPoint Relay Output Modules, Series A 11 ArmorPoint Relay Output Modules (continued) Power Rating (steady state) 1738-OW4M12 only 60W max. for 28.8V dc resistive output 60VA max. for 28.8V dc inductive output 1738-OW4M12AC only 60W max. for 28.8V dc resistive output 60VA max. for 28.8V dc inductive output 250W max. for 125V ac resistive output 480W max. for 240V ac resistive output 24W max. for 48V dc resistive output 31W max. for 125V dc resistive output 250VA max.
ArmorPoint Relay Output Modules, Series A General Specifications (continued) Shock Vibration ESD Immunity Radiated RF Immunity EFT/B Immunity Surge Transient Immunity Conducted RF Immunity Emissions Enclosure Type Rating Mounting Base Screw Torque Wiring Category2 Weight Imperial (Metric) Certifications: (when product is marked) IEC60068-2-27 (Test Ea, Unpackaged Shock): Operating 15g Non-operating 50g IEC60068-2-6 (Test Fc, Operating): 2g @ 10-500Hz IEC 61000-4-2: 6kV contact discharges 8kV air di
ArmorPoint Relay Output Modules, Series A 13 Notes: Publication 1738-IN008A-EN-E - June 2004
Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.