Manual

10 ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A
Publication
1738-IN025C-EN-P - March 2010
Interpret the Status Indicators
1738-OE4CM12
Status Indicators
Indicator State Description
Module
Status
Off No power applied to device.
Green Device operating normally.
Flashing green Device needs commissioning due to missing,
incomplete, or incorrect configuration.
Flashing red Recoverable fault.
Red Unrecoverable fault - may require device replacement.
Flashing
red/green
Device is in self-test.
MOD
NET
0
1
1738-OE4CM12/A
Analog Current Out
0
1
2
3
2
3
Module Status Indicators
44369
Network Status Indicators
I/O Status Indicators