Installation Instructions ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A Catalog Number 1738-OE4CM12 Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 3 About the Module 4 Mount the I/O Base 5 Install the Module 6 Remove the Module From the Mounting Base 7 Wire the Module 8 Communicate With Your Module 8 Interpret the Status Indicators 10 Specifications 12
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A 3 Environment and Enclosure ATTENTION This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A ATTENTION ATTENTION Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements. To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV). About the Module The ArmorPoint I/O family (Cat. no.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A 5 Mount the I/O Base To mount the ArmorPoint I/O base on a wall or panel, use the screw holes provided in the ArmorPoint base . The ArmorPoint I/O module must be mounted on a grounded metal mounting plate or other conductive surface. IMPORTANT Mounting illustration for the ArmorPoint adapter with I/O bases Adapter 46.25 mm (1.8 in) 51.9 mm (2.0 in) 20.1 mm (0.8 in) 51.9 mm (2.0 in) 20.1 mm (0.8 in) 51.9 mm (2.0 in) 56 mm (2.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A Mounting base 43675 Set to keyswitch position to 4 for the 1738 analog output modules Ground lug connection Latching mechanism Install the Module Follow the instructions to install the analog output module. 1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 4 aligns with the notch in the base. 2. Position the module vertically above the mounting base. The module bridges two bases.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A 7 Module bridges two bases. 1738-OE4CM12/A Analog Current Out 1 0 MOD NET 0 2 3 1 2 3 44370 3. Push the module down until it engages the latching mechanism. You will hear a clicking sound when the module is properly engaged. The locking mechanism locks the module to the base. Remove the Module From the Mounting Base Follow the instructions to remove the module from the mounting base. 1.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A Wire the Module 1738-OE4CM12 (view into connector) Pin 1 - Output Pin 2 - 24V dc Pin 3 - Common Pin 4 - Common Pin 5 - No Connect 44315 IMPORTANT ATTENTION Analog modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques. Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A 9 Default Data Map for the Module 1738-OE4CM12 Message size: 4 Bytes 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Produces (Scanner Rx) High Byte - Channel 1 Status Not used H C A L C A Low Byte - Channel 0 Status C M C F High Byte - Channel 3 Status Not used H C A L C A Not used H C A L C A C M C F C M C F Low Byte - Channel 2 Status C M C F Not used H C A L C A Where: CF = Channel Fault Status, 0 = no error, 1 = fault CM
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A Interpret the Status Indicators 1738-OE4CM12 1738-OE4CM12/A Analog Current Out 1 0 Module Status Indicators Network Status Indicators MOD NET 0 2 3 1 2 I/O Status Indicators 3 44369 Status Indicators Indicator State Description Module Status Off No power applied to device. Green Device operating normally. Flashing green Device needs commissioning due to missing, incomplete, or incorrect configuration.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A 11 Status Indicators (Continued) Indicator State Description Network Status Off Device is not on line: - Device has not completed dup_MAC-id test. - Device not powered - check module status indicator. Flashing green Device is on line but has no connections in the established state. Green Device is on line and has connections in the established state. Flashing red One or more I/O connections in timed-out state.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A Specifications General Attribute Value Outputs per module 4 single ended, nonisolated Output current 0 mA output until communication established 0…21 mA user configurable Resolution 16 bits 0.32 μA/cnt Absolute accuracy, 0.4% (0.1% if calibrated) min(1) Accuracy drift w/temp.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A 13 General (Continued) Attribute Value Special functionality Open wire detect, integer scaling Calibration possible for better accuracy Programmable Low, Low Low, High, and High High range alarms Thermal dissipation, max, at 28.8V dc 750 Ω load on each output - 6.34 BTU/hr 0 Ω load on each output - 7.
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A Environmental Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…60 °C (-4…140 °F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat): -40…85 °C (-40…185 °F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
ArmorPoint 4-Channel 24V dc Analog Output Modules, Series A 15 Environmental (Continued) Attribute Value EFT/B immunity IEC 61000-4-4: ±3 kV at 5 kHz on signal ports Surge transient immunity IEC 61000-4-5: ±1 kV line-line (DM) on signal ports ±2 kV line-earth (CM) on signal ports Conducted RF immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz Certifications Certification (when Value product is marked)(1) CE European Union 2004/108/EC EMC Directive, compliant with: EN 6
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.