Manual

Publication 1738-IN021A-EN-E - January 2007
8 ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics
Data Map - Produced Assembly Instance 23
Default Data Map - Configuration Assembly Instance 103
Message Size: 1 Bytes
7 6 5 4 3 2 1 0
Produce 0 (Rx) Fault
3
Fault
2
Fault
1
Fault
0
Input
3
Input
2
Input
1
Input
0
Consume (Tx) No consumed data
Where: Fault = open wire or short circuit.
Message Size: 18 Bytes
7 6 5 4 3 2 1 0
Consume 0 Input 0 Off to On Filter Byte 0
Consume 1 Input 0 Off to On Filter Byte 1
Consume 2 Input 0 On to Off Filter Byte 0
Consume 3 Input 0 On to Off Filter Byte 1
Consume 4 Input 1 Off to On Filter Byte 0
Consume 5 Input 1 Off to On Filter Byte 1
Consume 6 Input 1 On to Off Filter Byte 0
Consume 7 Input 1 On to Off Filter Byte 1
Consume 8 Input 2 Off to On Filter Byte 0
Consume 9 Input 2 Off to On Filter Byte 1
Consume 10 Input 2 On to Off Filter Byte 0
Consume 11 Input 2 On to Off Filter Byte 1
Consume 12 Input 3 Off to On Filter Byte 0
Consume 13 Input 3 Off to On Filter Byte 1
Consume 14 Input 3 On to Off Filter Byte 0
Consume 15 Input 3 On to Off Filter Byte 1
Consume 16 Autobaud
Disabled
Enable
OW3
Enable
OW3
Enable
OW3
Enable
OW3
Consume 17 Produced Assembly Instance
Produce (Tx) No produced data
Where: OW = open wire.