Owner's manual
1738 ArmorPOINT I/O Dual Port EtherNet/IP Adapter 11
Publication 1738-IN030A-EN-P - July 2013
Interpret Status Indicators
Refer to the following diagram and table for information on how to interpret the
status indicators.
ArmorPOINT I/O Dual Port EtherNet/IP Adapter, Series B
Indicator Status for Modules
Indicator State Description
Adapter
status
Off No power applied to device
Flashing green Device needs commissioning due to missing, incomplete, or
incorrect configuration.
Solid green Device operating normally
Flashing red Recoverable fault.
Complete firmware update, verify address switches.
Solid red Unrecoverable fault:
•Self-test failure (checksum failure, RAM test failure at cycle power)
•Firmware fatal error).
Flashing
red/green
Module self-test
Adapter Status indicator
Network Activity indicator
Network Status indicator
System Power indicator
Adapter Power indicator
POINTBus Status
1738-AENTR
Series B
EtherNet I/P
Adapter
Status
Network
Activity
Network
Status
PointBus
Status
System
Power
Adapter
Power
conformance tested
™
PWR
IP ADDRESS
Link 2
Activity/
Status
Link 1
Activity/
Status
44830
Link 1 Activity/Status
indicator
Link 2 Activity/Status
indicator