User Manual POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP Adapters Catalog Numbers 1734-AENTR, 1738-AENTR, Series A
Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
Preface Read this preface to familiarize yourself with the rest of the manual. It provides information concerning: • who should use this manual • the purpose of this manual • related documentation • conventions used in this manual Who Should Use this Manual Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Series A 1734 POINT I/O™ or 1738 ArmorPOINT I/O™ 2 Port EtherNet/IP Adapter Modules.
Common Techniques Used in this Manual The following conventions are used throughout this manual: • Bulleted lists such as this one provide information, not procedural steps. • Numbered lists provide sequential steps or hierarchical information. • Italic type is used for emphasis. Rockwell Software products contain extensive tutorials and help screens. We recommend that you use these tutorials and help screens to learn about the products.
Table of Contents Preface Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i Common Techniques Used in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . ii Chapter 1 About the Adapters Overview . . . . . . . . . . . . .
Table of Contents Gateway Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Subnet Mask . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set the Network Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set the Network Address for POINT I/O Adapter . . . . . . . . . . . . . . Set the Network Address for ArmorPOINT I/O Adapter. . . . . . . .
Table of Contents Chapter 6 Troubleshoot the Adapter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interpret the Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Status Indicators for POINT I/O Adapter. . . . . . . . . . . . . . . . . . . . . . Status Indicators for ArmorPOINT I/O Adapter . . . . . . . . . . . . . . .
Table of Contents vi Rockwell Automation Publication 1734-UM014B-EN-P - August 2013
Chapter 1 About the Adapters Overview This chapter provides an overview of the Series A1734-AENTR POINT I/O and 1738-AENTR ArmorPOINT I/O EtherNet/IP adapters, their primary features, and how to use them. You need to understand the concepts discussed in this chapter to configure your adapter and use it in an EtherNet/IP control system. This table lists where to find specific information.
Chapter 1 About the Adapters About the POINT I/O and ArmorPOINT I/O 2 Port Adapters The POINT I/O and ArmorPOINT I/O adapters provide connectivity to EtherNet/IP networks for POINT I/O and ArmorPOINT I/O modules respectively. The POINT I/O adapter is for the I/O backplane that provides connectivity through two RJ-45 connectors for 2-port pass-through support of daisy chain or ring, and the existing star and tree network topologies.
About the Adapters Chapter 1 In an attempt to address these situations, you must observe the following rules for I/O system construction and the removal and reinsertion of modules. • A correct I/O system does not have any empty terminal bases. • After you cycle power, the adapter will not allow any I/O connections until the number of modules comprising the chassis plus one for the adapter equals the stored chassis size.
Chapter 1 About the Adapters When you first apply power, we expect that all but one module on the backplane exhibits a solid red Module Status LED. One by one the adapter resets these modules and addresses them appropriately. The amount of time that this operation takes is proportional to the size of your I/ O system.
About the Adapters Hardware/Software Compatibility Chapter 1 The I/O adapters and the applications described in this manual are compatible with the following firmware revisions and software releases. Contact Rockwell Automation if you need software or firmware upgrades to use this equipment Use of the Common Industrial Protocol (CIP) Product Firmware Revision/ Software Release 1734-AENTR; 1738-AENTR adapters 3.xx or later 1756-ENBT 2.
Chapter 1 About the Adapters The controller also produces data for other controllers to consume. The produced and consumed data is accessible by multiple controllers and other devices over the EtherNet/IP network. This data exchange conforms to the producer and consumer model. Specify the Requested Packet Interval (RPI) The Requested Packet Interval or RPI is the update rate specified for a particular piece of data on the network.
About the Adapters Chapter 1 eight I/O modules. If you use a rack-optimized connection to transfer the data, you only need a single connection – the connection to the I/O adapter. IMPORTANT Although rack-optimized connections offer an efficient way to use resources, there are a few limitations on their use: • You can use only rack-optimized connections to send data to and from digital I/O modules. Analog or speciality I/O requires direct connections.
Chapter 1 About the Adapters Notes: 8 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Chapter 2 Install Your Adapter Overview This chapter describes how to physically install the Series A POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP adapters; and how to connect the adapter to the EtherNet/IP network. The only tools you require are a flat or Phillips head screwdriver and a drill. This table lists where to find specific information.
Chapter 2 Install Your Adapter Identify Adapter Components Use the figures to identify the external features of your I/O adapters.
Install Your Adapter Chapter 2 Mount the I/O Adapter Use the following procedures to mount the I/O adapters on a new system before you install any I/O modules. Mount a 1734-FPD module in the slot next to the I/O adapter when applying field power. You can also use the 24V DC to power the adapter to supply field power, where no FPD is necessary. Refer to Point I/O Field Potential Distribution Module Installation Instructions, publication 1734-IN059 for more information.
Chapter 2 Install Your Adapter 5. Slide the safety end cap up to remove it, exposing the backplane and power interconnections. WARNING: If you connect or disconnect the Ethernet cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Install Your Adapter Chapter 2 Terminating Base Keyswitch Mounting hole Ground connection Latching mechanism hole Latching mechanism release 43787 Install the POINT I/O Adapter Module To install the adapter on the DIN rail prior to installing other base units: ATTENTION: Allow 25.4 mm (1.0 in.) of space between adjacent equipment for adequate ventilation. 1. Position the adapter vertically above the DIN rail. 2.
Chapter 2 Install Your Adapter Install the ArmorPOINT I/O Adapter Module To install the ArmorPOINT I/O adapter module: 1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the appropriate number for the I/O module you are installing aligns with the notch in the base. Refer to the installation instructions for each module to determine what this number must be. See Related Documentation on page i for a list of these installation instructions. 2.
Install Your Adapter Chapter 2 Wire the ArmorPOINT I/O Adapter Wire the EtherNet/IP and auxiliary power connectors on the adapter as shown.
Chapter 2 Install Your Adapter Notes: 16 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Chapter 3 Configure the Adapter for Your EtherNet/ IP Network Overview Before using your adapter in an EtherNet/IP network, you need to configure it with an IP address, subnet mask, and optional Gateway address. This chapter describes these configuration requirements and the procedures for providing them. Here are ways you can do this: • Use the Rockwell BootP/DHCP utility, version 2.3 or later, that ships with RSLogix 5000 or RSLinx software.
Chapter 3 Configure the Adapter for Your EtherNet/IP Network Configuration Requirements Before you can use your adapter, you must configure its IP address, its subnet mask, and, optionally, a gateway address. You can use the Rockwell BootP utility, version 2.3 or later, to perform the configuration. You can also use a DHCP server or the network address switches to configure these parameters. ATTENTION: You must use series C POINT I/O modules with the adapter.
Configure the Adapter for Your EtherNet/IP Network Chapter 3 Gateway Address This section applies to multi-network systems. If you have a single network system, refer to the next section. The Gateway Address is the default address of a network. It provides a single domain name and point of entry to the site. Gateways connect individual physical networks into a system of networks. When a node needs to communicate with a node on another network, a gateway transfers the data between the two networks.
Chapter 3 Configure the Adapter for Your EtherNet/IP Network Subnet Mask The subnet mask is used for splitting IP networks into a series of subgroups, or subnets. The mask is a binary pattern that is matched up with the IP address to turn part of the Host ID address field into a field for subnets. EXAMPLE Take Network 2 (a Class B network) in the previous example and add another physical network.
Configure the Adapter for Your EtherNet/IP Network Set the Network Address Chapter 3 The adapters ship DHCP-enabled and with the switches set to 999. To change the network address, do the following. Set the Network Address for POINT I/O Adapter • Use the thumbwheel switches located on the adapter. Press either the + or buttons to change the number. • Use a Dynamic Host Configuration Protocol (DHCP) server, such as Rockwell Automation BootP/DHCP. • Retrieve the IP address from non-volatile memory.
Chapter 3 Configure the Adapter for Your EtherNet/IP Network Set the Network Address for ArmorPOINT I/O Adapter • Adjust the switches in front of the module • Use a Dynamic Host Configuration Protocol (DHCP) server such as Rockwell Automation BootP/DHCP • Retrieve the IP address from non-volatile memory The adapter reads the switches first to determine if the switches are set to a valid number. Set the network address by adjusting the three switches on the front of the adapter.
Configure the Adapter for Your EtherNet/IP Network Chapter 3 To configure your adapter using the BootP utility, perform the following steps: 1. Run the BootP software. In the BOOTP Request History panel you see the hardware addresses of devices issuing BootP requests. 2. Double-click the hardware address of the device you want to configure.
Chapter 3 Configure the Adapter for Your EtherNet/IP Network The New Entry dialog appears with the device’s Ethernet Address (MAC). 3. Enter the IP Address you want to assign to the device and click OK. The device is added to the Relation List, displaying the Ethernet Address (MAC) and corresponding IP Address, Hostname, and Description (if applicable). When the address displays in the IP Address column in the Request History section, the IP address assignment has been made. 4.
Configure the Adapter for Your EtherNet/IP Network Chapter 3 Save the Relation List You can save the Relation List for later use. To save the Relation List, perform the following steps: 1. Select Save As... from the File menu. The Save As dialog appears. 2. Select the folder where you want to save the Relation List. 3. Enter a File name for the Relation List, for example, control system configuration, and click Save. You can leave the Save as type at the default setting: Bootp Config Files (*.bpc).
Chapter 3 Configure the Adapter for Your EtherNet/IP Network Use DHCP Software to Configure Your Adapter DHCP (Dynamic Host Configuration Protocol) software automatically assigns IP addresses to client stations logging onto a TCP/IP network. DHCP is based on BootP and maintains some backward compatibility. The main difference is that BootP was designed for manual configuration, while DHCP allows for dynamic allocation of network addresses and configurations to newly attached devices.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software Overview In this example, a ControlLogix controller communicates with I/O modules via the adapter using a direct connection. The adapter makes a direct connection to each of the modules referenced by the data. The modules presented in this chapter use RSLogix 5000 software, revision 11 and above. ATTENTION: You must use series C POINT I/O modules with the adapter. Series A or B POINT I/O modules do not work with the adapter.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software To work along with this example, set up your system as shown in the figure. 1734-AENTR 10.88.70.2 Slot 0 1 2 3 Local chassis POINT I/O Link 1 Activity/ Status Data Link 2 Activity/ Status L63 controller (slot 1) 1756-ENBT 10.88.70.4 (slot 3) Slot 0 1 2 3 4 Switch 10.88.70.26 Programming terminal 45176 • In the example application, we assume that the L63 controller and 1756ENBT module (firmware revision 2.
Configure the Adapter for Direct Connection in RSLogix 5000 Software Create the Example Application Chapter 4 Perform the following steps to create the example application: 1. Start RSLogix 5000 Enterprise Series software to open the RSLogix 5000 main dialog. 2. From the File menu, select New. 3. The New Controller dialog opens. 4. Enter an appropriate Name for the Controller, for example, POINT_IO_Controller.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software 5. Select the correct Version, Chassis Type, and Slot number of the L63 controller, and the folder where you want to save the RSLogix 5000 file (Create In). The Description is optional. RSLogix 5000 software version 18 lets you enable redundancy. To use redundancy in your system, check the Redundancy Enabled checkbox when using the said version or later. 6. Click OK.
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4 The Select Module dialog opens. 3. Expand the Communications tree as in the following dialog. 4. Select the 1756-ENBT EtherNet/IP Bridge and click OK. The Select Major Revision dialog opens. 5. Select the number for Major Revision and click OK.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software The New Module dialog opens. 6. Enter values for Name, IP Address, Slot, Electronic Keying, and Revision, noting that we used the following values: Name IP Address Slot Electronic Keying Revision Local_ENBT 10.88.70.4 3 Compatible Keying 3.1 7. Click OK to accept the configuration. The Module Properties dialog opens.
Configure the Adapter for Direct Connection in RSLogix 5000 Software Add the POINT I/O Adapter to the I/O Configuration Chapter 4 Next, you must add the adapter as a child of the local 1756-ENBT module. 1. In the Project dialog, right-click the local 1756-ENBT module under the I/O Configuration folder, and select New Module from the dialog. The Select Module dialog opens. 2. Expand the Communications tree.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software 3. Select your adapter from the list, and click OK, noting that we entered these values on the General Tab of the New Module dialog.. Name IP Address IMPORTANT POINT_IO_Adapter 10.88.70.2 The Slot field appears grey because the slot is automatically 0 for the 1734-AENTR adapter. The New Module dialog opens. 4. Click Change... The Module Definition dialog opens. 5.
Configure the Adapter for Direct Connection in RSLogix 5000 Software IMPORTANT Chapter 4 The chassis size value equals 1 for the adapter plus the number of I/O modules installed (physically present on the I/O backplane). Connection choices are the following: • None – the adapter only makes a direct connection to each of the modules referenced by the data. • Rack optimization – digital I/O data is collected into a rack image. This rack image does not include analog or specialty I/O modules.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software In this example, you add a 1734-OW2 relay output and a 1734-OV4E sink output modules with standard configurations. Use these steps as a guide when configuring different I/O modules for your system. TIP This example application uses I/O module default configurations. For more information, refer to the POINT I/O Selection Guide, publication 1734-SG001. Add the Relay Output Module 1.
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4 The New Module dialog opens. 4. Enter values for Name and Slot, noting that we used the following values. Name Slot POINT_Relay_Output 1 5. Choose Connection. The RPI is selectable since it is a direct connection. 6. Enter 50 for requested packet interval (RPI) to set how often you exchange data with the I/O adapters.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software Add the Digital Output Module 1. Right-click the name of the I/O adapter and select New Module. The Select Module dialog opens. Expand the Digital tree. 2. Select the 1734-OV4E digital output module from the list.
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4 3. Click OK. The New Module dialog opens. Enter values for Name and Slot, noting we used the following. Name Slot POINT_Digital_Output 2 4. On the Connection tab, enter 10 ms as the RPI for the 1734-OV4E module. 5. Click OK.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software Edit the Controller Tags When you add modules to the I/O configuration the system creates tags for those modules to use in the application program. For the example application you need to add one more controller tag. 1. Double-click the Controller Tags folder in the project dialog. The Controller Tags dialog opens. You see the tags created for the 1734AENTR adapter and its digital I/O modules.
Configure the Adapter for Direct Connection in RSLogix 5000 Software Create the Ladder Program Chapter 4 Create the example ladder program to test the I/O. 1. Under the Main Program folder, double-click Main Routine. 2. Enter the following ladder program using the tags previously created. 3. Save the program. Download the Program to the Controller Follow this procedure to download the program you just saved to the ControlLogix controller. 1. From the main menu, choose Communications>Who-Active.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software 4. Choose Download. The Download dialog opens with a reminder of the following. • The controller is in Remote Run mode. • The mode changes to Remote Program prior to download. 5. From the Download dialog, choose Download The RSLogix 5000 software dialog opens. 6. Notice that the 1756-ENBT Bridge is now online. If yellow triangles are present, see the following section.
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4 3. Select Properties. 4. Click the Connection tab. The Module Fault error code displays. 5. Click the Chassis Size tab. 6. Click Set Chassis Size in Module.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software 7. Read and acknowledge the warning dialog. 8. Click OK to continue. Notice the chassis size stored in the module has been changed to 3. At this point, your POINTBus status LED should be solid green. All the yellow triangles in your I/O configuration should be gone. 9. Click OK.
Configure the Adapter for Direct Connection in RSLogix 5000 Software Configure the Adapter with Fixed IP Address Chapter 4 To configure the adapter with a fixed IP address to prevent the adapter from ceasing to communicate with the ControlLogix controller: 1. All controllers with I/O connections to the AENTR and/or the modules in its backplane need to be in program mode. 2. In the Module Properties dialog, click the Port Configuration tab. 3. Unselect the Enable DHCP box. 4. Click the Set button. 5.
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software Recover From an Overloaded Adapter Each I/O connection established with the I/O adapter consumes a portion of microprocessor bandwidth. The amount of bandwidth used by a connection depends on several variables, such as the requested packet interval (RPI), number of I/O modules involved in the connection, and rate of change of the I/O.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Overview This chapter guides you through the steps required to configure your AENTR adapter with both direct and rack-optimized I/O connections using RSLogix 5000 software. You can mix I/O connection formats for different I/O modules communicating through the same adapter. I/O modules set up to use rack optimization communicate at the rate of the RPI configured for the adapter.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Set Up the Hardware The following section describe how to set up the I/O Hardware. Set Up the POINT I/O Hardware In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a 1756-ENBT bridge module in slot 3.
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Create the Example Application Chapter 5 Perform the following steps to create the example application: 1. Start the RSLogix 5000 Enterprise Series software. The RSLogix 5000 software main dialog opens. 2. From the File menu, select New. 3. The New Controller dialog opens. 4. Enter an appropriate Name for the Controller, for example, POINT_IO_Controller. 5.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Configure the I/O Modules You now add the I/O modules to the controller I/O configuration. To do this, first add the local 1756-ENBT module to the I/O configuration. Next, add the I/ O adapter as a child of the 1756-ENBT module, and then add the I/O modules as children of the adapter.
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5 3. Expand the Communications tree, as in the following dialog and select the 1756-ENBT EtherNet/IP Bridge. 4. Click OK. The Select Major Revision dialog opens. 5. Select the value for Major Revision and click OK. The Module Properties dialog opens. 6.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 7. Click OK to accept the configuration. Add the I/O Adapter to the I/O Configuration Next, you must add the I/O adapter as a child of the local 1756-ENBT module. 1. In the Project dialog, right-click the local 1756-ENBT module under the I/O Configuration folder, and select New Module from the dialog. The Select Module dialog opens.
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5 2. Expand the Communications tree and select the 1734-AENTR Ethernet Adapter from the list. 3. Click OK. The New Module dialog opens. 4. Enter values for Name and IP Address, noting we used the following values. Name IP Address IMPORTANT Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 POINT_IO_Adapter 10.88.70.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 5. On the General tab, click Change... The Module Definition dialog opens. 6. Enter values for Connection, Chassis Size, Electronic Keying, and Revision. Connection Chassis Size Electronic Keying Revision IMPORTANT Rack Optimization 5 Compatible Module 3 The chassis size equals 1 for the adapter plus the number of I/O modules installed (physically present on the I/O backplane).
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5 The New Module properties dialog opens. 9. Verify that the requested packet interval (RPI) is appropriate for your system. You use this value for the rack-optimized connection to the I/O modules. IMPORTANT To avoid overloading the adapter, we recommend that you set RPI no less than 10 ms for rack connections and 50 ms for direct connections. 10. Click OK. The name of the adapter appears in the I/O tree.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Add the POINT I/O Module and Configure for Rack-optimized Connection 1. Right-click the POINT I/O Chassis in the I/O Configuration folder and select New Module… The Select Module dialog opens. 2. Expand the Digital tree. 3. Select the 1734-OW2 relay output module from the list and click OK.
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5 The New Module dialog opens. 4. Click Change... and then enter values for Name and Slot, noting we used the following values. Name Slot POINT_Relay_Output 1 5. Note that the requested packet interval (RPI) is the same as was chosen by the adapter. You use this value for the rack-optimized connection to the I/ O modules.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Add the POINT I/O Module and Configure For Direct Connection 1. Right-click the POINT I/O Chassis in the I/O Configuration folder, and select New Module. IMPORTANT If you exceed the adapter chassis size trying to add more modules than you configured, the New Module selection appears dim and is disabled. Increase the adapter chassis size to add more I/O modules. The Select Module dialog opens. 2.
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5 3. Choose the 1734-OV4E/C module and click OK. The New Module dialog opens.. 4. From the New Module dialog, complete the following: – Enter a value for Name. – Enter a value for Slot. – Click Change to modify the module definition values. The Module Definition dialog opens. 5. For Connection, select Data. This configures the controller to make a Direct I/O Connection to the module. 6. Click OK.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 7. From the New Module dialog, click the Connection tab. The New Module dialog opens. 8. From the New Module dialog, enter 50 for the Requested Packet Interval (RPI). 9. Keep the following unchecked. a. Inhibit Module b. Major Fault on Controller If Connection fails While in Run Mode 10. Click OK. 11. Choose File →Save and enter the name and location of the file.
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5 3. Click Set Project Path. 4. Click Download. The Download dialog opens. 5. From the Download dialog, click Download. The Downloading dialog displays the download progress. Notice that the 1756-ENBT Bridge is now online. If yellow triangles are present, see the following section.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 4. Click the Connection tab. The Module Fault error code displays at the bottom of the Connection tab. 5. Click the Chassis Size tab. 6. Click Set Chassis Size in Module.
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5 7. Read and acknowledge the warning dialog. 8. Click OK to continue. 9. Notice the chassis size in the module is modified to 5. 10. Click OK. At this point, your POINTBus status LED should be solid green. All the yellow triangles in your I/O configuration should be gone. 11. Click OK to close the dialog. 12. Click File →Save to save the project.
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Access Module Data Use the following information to use the I/O adapter data in the ladder logic program: • POINT_IO_Adapter — the name you gave to your EtherNet adapter • # — slot number of POINT I/O module • C — configuration, I = input, O = output Use the controller tags in your ladder program to read input data or write output data.
Chapter 6 Troubleshoot the Adapter Overview This chapter describes the different status indicators available in the 1734 POINT I/O and 1738 ArmorPOINT I/O EtherNet/IP adapters and how to interpret these indicators to help troubleshoot the modules.
Chapter 6 Troubleshoot the Adapter Status Indicators for 1734-AENTR Adapter Module status Network status Network Activity Link 1 or Link 2 Activity / Status POINTBus status Status Description Off No power applied to device Solid green Device operating normally Flashing red/green Module self-test Flashing red Recoverable fault. Complete firmware update, verify address switches. Solid red Unrecoverable fault, may require device replacement.
Troubleshoot the Adapter Chapter 6 Status Indicators for 1734-AENTR Adapter System power Field power Status Description Off Not active. Adapter power is off, or there is a DC-DC converter problem. Solid green System power is on. DC-DC converter output is active (5V). Off Not active. Adapter power is off. Solid green Power is on. 24V input is present.
Chapter 6 Troubleshoot the Adapter Status Indicators for ArmorPOINT I/O Adapter The following describes the status indicators on the 1738-AENTR.
Troubleshoot the Adapter Chapter 6 Status Indicators for 1738-AENTR Adapter Network activity Network status System power Adapter power POINTBus status Link 1 or Link 2 activity/status Status Description Off No link established with Port 1 or Port 2. Green Link established with Port 1 and/or Port 2 at 100 Mbps. Link established with Port 1 and Port 2. One port at 100 Mbps and one port at 10 Mbps Flashing green Transmit or receive activity present on Port 1 and/or Port 2 at 100 Mbps.
Chapter 6 Troubleshoot the Adapter Notes: 70 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Appendix A EtherNet/IP I/O Adapter Specifications Specifications Following are specifications for the POINT I/O and ArmorPOINT I/O modules General Specifications – POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP Adapters 1734-AENTR, 1738-AENTR Specification Description Module location Starter module - left side of the 1734 system LED Indicators Adapter status - green/red Network status - green/red POINTBus status - green/red Network activity - green System power (POINTBus 5V power) - green Field po
Appendix A EtherNet/IP I/O Adapter Specifications Specifications – POINT I/O 2 Port EtherNet/IP Adapter 1734-AENTR Specification Description Expansion I/O capacity • Maximum of 63 modules • Maximum of 5 Rack Optimized connections (for digital modules only) • Maximum of 20 Direct connections • POINT I/O 1734-AENTR backplane current output= 0.8 A maximum. The actual number of modules varies.
EtherNet/IP I/O Adapter Specifications Appendix A Specifications – POINT I/O 2 Port EtherNet/IP Adapter 1734-AENTR Specification Description Expansion I/O capacity 1734-OE4C75 mA 1734-IA475 mA 1734-IM475 mA 1734-OA475 mA 1734-IR2E75 mA 1734-8CFG100 mA Ethernet communication rate 10/100 Mbps, half or full-duplex Module location Starter module - left side of the 1734 system Dimensions (HxWxD), approx. 76.2 x 73.0 x 133.4 (3.0 x 2.87 x 5.25) Weight, approx. 280 g (9.
Appendix A EtherNet/IP I/O Adapter Specifications Specifications – AmorPOINT I/O 2 Port EtherNet/IP Adapter 1738-AENTR Specification Description Expansion I/O capacity • Maximum of 63 modules • Maximum of 5 Rack Optimized connections (for digital modules only) • Maximum of 20 Direct connections • 1738-AENTR backplane current output =0.8 A. The actual number of modules varies. Add up the current requirements of the modules you want to use to make sure they do not exceed the amperage limit of 0.8 A.
EtherNet/IP I/O Adapter Specifications Appendix A Environmental Specifications Specification Description Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…55 °C (-4…131 °F) – 1734-AENTR -20…60 °C (-4…140 °F) – 1738-AENTR Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged
Appendix A EtherNet/IP I/O Adapter Specifications Certifications Certifications (when product is marked)(1) Value c-UL-us 1734-AENTR only UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584 UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab.
Appendix B Adapter Web Dialogs Overview Work with the Home Page The Web dialog of the I/O adapter offers extensive internal and network diagnostics. To view the Web dialogs, enter the IP address of the I/O adapters into your browser.
Chapter B Adapter Web Dialogs To display and work with the adapter diagnostics home page, follow these procedures. IMPORTANT Make sure that your PC Internet LAN setting and your TCP/IP settings are configured to access the subnet on which your adapter communicates. 1. From your web browser, enter the adapter IP address to see the Home page. Enter the adapter IP address to see the home page. 2.
Adapter Web Dialogs Chapter B • Click Rockwell Automation at the top right to go to www.rockwellautomation.com. • Click the following to see additional diagnostics web pages. – Diagnostics - Diagnostic overview, Network Settings, Ethernet Statistics, I/O Connections, Diagnostic messaging – Configuration - Identity, Network, Services – Browse Chassis Work with the Diagnostics Pages To work with the Diagnostics options, follow these procedures. 1.
Chapter B Adapter Web Dialogs 1. Click Diagnostic Overview from the tab at the top of the page or panel on the left. The Diagnostic Overview page opens. 2.
Adapter Web Dialogs Chapter B – Conn Closes – Close Errors – Conn Timeout – Status • Module Settings – Chassis Size – Switches Use the Network Settings Page To use the Network Settings page for network related information, follow this procedure. 1. Click Network Settings from the tab at the top of the page or panel on the left. This opens the Network Settings page. 2.
Chapter B Adapter Web Dialogs – Host Name – Name Resolution • Ethernet Interface Configuration – How the Network Configuration was obtained - Static or Dynamic • Ethernet Link – Media Speed – Half or Full Duplex – Autonegotiate Status Use the Ethernet Statistics Page To use the Ethernet Statistics page for information about the Ethernet link and interface and media counters, use this procedure. 1. Click Ethernet Statistics from the tab at the top of the page or panel on the left.
Adapter Web Dialogs Chapter B • Interface Counters – In Octets, In UCast Packets, In NUcast Packets, In Discards, In Errors, In Unknown Protos, Out Octets, Out Ucast Packets, Out NUcast Packets, Out Discards, Out Errors • Media Counters – Alignment Errors – FCS Errors – Single Collisions – Multiple Collisions – SQE Test Errors – Deferred Transmissions – Late Collisions – Excessive Collisions – MAC Transmit Errors – Carrier Sense Errors – Frame Too Long – MAC Receive Errors Use the I/O Connections Page To
Chapter B Adapter Web Dialogs • • • • • • • • • • Connection Number Uptime Receive and Transmit (Rcv/Xmt) Connection ID Source IP Address with an indication of the following: – (O) for originator – (T) for target Destination IP Address Multicast Address Requested Packet Interval (RPI) Lost/Slot that shows the number of lost packets and the slot number for the connection, with a slot value of 0 indicating that this is a rackoptimized connection Size of data in bytes Use the Diagnostic Messaging Page To
Adapter Web Dialogs Chapter B • Attribute (decimal) • Timeout 3. From the Diagnostic Messaging page, click Submit to see values similar to that shown. Work with the Configuration Pages To work with the Configuration pages, follow these procedures. IMPORTANT The values on these pages are in non-volatile memory. Changes to these parameters do not take effect until you reset or cycle power through the I/O adapters.
Chapter B Adapter Web Dialogs 1. From the Home page, click Configuration or Expand to see the Configuration options, if needed. 2. From the Configuration page, click one of the following: • Identity • Network • Services A login dialog opens as shown. The dialog may vary in appearance depending on your operating system and browser. 3. From the user name and password dialog, enter values, noting the following: • The values for user name and password are case sensitive. • The default user name is admin.
Adapter Web Dialogs Chapter B The Identity page opens 2. From the Identity page, complete entries for the following, noting that the description and location help you identify where modules are in the facility: • Host Name – the name a Domain Name Server uses to resolve this adapter’s IP address • Module Description • Module Location • Chassis Size - the value that shows the number of I/O modules plus the adapter.
Chapter B Adapter Web Dialogs 1. Click Network from the tab at the top of the page or panel on the left. The Network Configuration page opens. 2. From the Network Configuration page, complete these entries, noting that values for Network Interface are disabled when DHCP is Dynamic DHCP and port speed and duplex mode are disabled when Autonegotiate Speed and Duplex is selected.
Adapter Web Dialogs Chapter B 3. From the Network Configuration page, click Apply Changes to save the modified values. Use the Services Page To use the Services page to change the password for the Configuration web page or disable the web server, complete these procedures. 1. Click Services from the tab at the top of the page or panel on the left. The Services page opens. 2. From the Services page, make these entries.
Chapter B Adapter Web Dialogs 1. From the Home page, click Browse Chassis. Check Increase timeout to increase time of the browse query and the time the modules get to respond to the query. This is useful when browsing a busy system. 2. From the Browse Chassis page, leave the Display compact check box unchecked, unless you want to decrease the font size, to make the full page easier to read after the query. 3.
Adapter Web Dialogs Chapter B After completing a query, here is how a typical Browse Chassis page looks with the module hyperlinks active and the Display compact check box unselected. Click a module hyperlink to view information about the module 5. To view information about a particular module, click the corresponding Module Description hyperlink.
Chapter B Adapter Web Dialogs Notes: 92 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Appendix C Configure the RSLinx Ethernet Communication Driver Overview To communicate with your adapter over your network, you must configure the RSLinx Ethernet Communication Driver (AB_ETH) or the EtherNet/IP driver (AB-ETHIP). You can configure the AB_ETH driver with the IP addresses of all the Ethernet devices on your system. You need one of these drivers to download the example application programs in this manual. See the table for a list of the contents of this appendix.
94 Configure the RSLinx Ethernet Communication Driver 2. From the Communications menu, select Configure Drivers. 3. Select Ethernet Devices from the list and click Add/New... 4. Select the default driver name (for example, AB_ETH-1) or type in a name and click OK. The Configure driver dialog opens.
Configure the RSLinx Ethernet Communication Driver 95 5. Click Add New and enter the IP address or Host Name of your Ethernet device (for example, 10.88.70.4, Pump1). 6. Repeat step 6 for each additional Ethernet device you need to access. 7. After entering the IP addresses, click Apply. 8. Click OK to close the Configure driver dialog. The new driver appears in the list of configured drivers. Your list displays the drivers you configured on your workstation. 9. Close the RSLinx software.
96 Configure the RSLinx Ethernet Communication Driver Configure the AB_ETH/IP Driver To configure the AB-ETHIP Ethernet communication driver, perform the following steps. 1. Start the RSLinx software. 2. From the Communications menu, select Configure Drivers. 3. Select EtherNet/IP Devices from the list and click Add/New...
Configure the RSLinx Ethernet Communication Driver 97 The Configure Driver dialog box opens. Make sure the Browse Local Subnet button is selected. The RSLinx software browses your local subnet and automatically reads the IP address. 4. Click OK. The AB-ETHIP driver is now configured and appears in the configured drivers window. 5. Close the RSLinx software.
98 Configure the RSLinx Ethernet Communication Driver Notes: Publication 1734-UM014B-EN-P - June 2013
Index Numerics 1734-AENTR 4 specifications 71, 73 1738-AENTR 4 specifications 71, 73 A adapter AENTR 46, 47 diagnostics 77 I/O 2 mounted 28 address fixed IP 45 Gateway 17, 19 IP 17, 26, 77, 78, 95 network 21 switches 18 Autonegotiate Status 82 B bandwidth insufficient 46 limit 46 used 46 BootP software 22 BootP/DHCP utility 22 C chassis ControlLogix 28 size 4, 88 chassis size set 4 CIP 6 Common Industrial Protocol 6 common techniques used in this manual ii conducted RF immunity 74 configuration 18, 78, 7
Index Ethernet cable 73 Ethernet communication rate 73 Ethernet connectors 73 Ethernet Interface Configuration 82 Ethernet network topologies supported 73 Ethernet ports 73 Ethernet wire connections 73 EtherNet/IP bridge 50 driver 93 Ethernet Industrial Protocol 6 F Field power output 72 Field power supply 72 Field side power 73 firmware revisions 4 G Gateway default 82 Gateway address 17, 19 H Home page 77, 79, 91 Host ID 20 Host Name 82, 95 host name 88 I I/O adapter 2, 46, 64 connection 46 direct co
Index Module Description 92 Module input 72 modules overview 9 Mounting type 72 N Network settings 79 network configuration 87 Network Address 17 thumbwheel 17 network address 21 network address switches 18 Network Configuration 87 Network Settings 81 O Overview 1734 POINT I/O and ArmorPOINT I/O Installation 9 P POINTBus output current 73 power consumption 72 Power dissipation 72 power up system for the first time 6 primary tasks 2 protocol message-based 6 publications related i purpose of this manual i
Index nonoperating 74 operating 74 Terminal base screw torque 72 Thermal dissipation 72 U upgrades firmware 4 software 4 Uptime 84 V vibration 74 W web dialogs 77 server 90 web dialogs 77 Advanced Diagnostics 85, 86 Browse Chassis 78, 79, 91 Diagnostic Overview 80 Ethernet Address 81 Ethernet Link 83 Ethernet Statistics 79, 82, 83 web page diagnostics 79 web server disable 90 Weight, approx.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.