Installation Instructions ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A Catalog Number 1738-AENTR Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 3 About the Module 4 Mount the Adapter and I/O Base 7 Set the Network Address 9 Wire the EtherNet/IP Adapter 10 Interpret the Status Indicators 11 Specifications 16
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 3 Environment and Enclosure ATTENTION This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A ATTENTION ATTENTION Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements. To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 5 1738-AENTR Adapter, Series A EtherNet I/P Link 1 Activity/ Status M12 connectors 1738-AENTR Link 2 Activity/ Status IP ADD RES S Network Activity Network address switches Auxiliary Power connector Adapter Status Network Status Status indicators PointBus Status System Power Adapter Power PWR ™ conformance tested 44830 Before You Begin To effectively use your adapter, note the following considerations.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A If using the adapter with a 1756-ENBT module, 1768-ENBT module or an L3xE processor, use the following required firmware versions for these bridge modules: • 1756-ENBT firmware version 4.5 or greater • 1768-ENBT firmware version 2.1 or greater • L3xE processor firmware version 17 or greater If you use the BootP utility to assign IP addresses to the adapter, use version 2.3.2 or greater.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 7 Mount the Adapter and I/O Base To mount the ArmorPoint I/O adapter on a wall or panel, use the screw holes provided with the ArmorPoint I/O adapter. IMPORTANT The ArmorPoint I/O adapter must be mounted on a grounded metal mounting plate or other conductive surface. Mounting illustration for the ArmorPoint I/O adapter with I/O bases Adapter 20.1 mm (0.8 in) 46.25 mm (1.8 in) 51.9 mm (2.0 in) 20.1 mm (0.8 in) 51.9 mm (2.0 in) 51.9 mm (2.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 4. Ground the system using the ground lug connection in the I/O base. (The ground lug connection is also a mounting hole.) Mounting base Set to keyswitch position to 4 for the 1738 analog output modules Ground lug connection 43675 Latching mechanism 5. Mount the terminating base that was shipped with the adapter as the last base in the backplane instead of the base that was shipped with the I/O module.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 9 Set the Network Address The adapter ships with the rotary network address switches set to 999 and DHCP enabled. To change the network address, you can: • adjust the switches on the front of the module • use a Dynamic Host Configuration Protocol (DHCP) server, such as Rockwell Automation BootP/DHCP • retrieve the IP address from nonvolatile memory The adapter reads the switches first to determine if the switches are set to a valid number.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A Refer to publication 1738-UM014, ArmorPoint I/O EtherNet/IP Adapter User Manual, for more information. Wire the EtherNet/IP Adapter Following are wiring instructions for the ArmorPoint EtherNet/IP adapter.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 11 Interpret the Status Indicators Link 1 Activity/Status indicator EtherNet I/P Link 1 Activity/ Status 1738-AENTR Link 2 Activity/Status indicator Link 2 Activity/ Status IP ADD RES S Adapter Status indicator Network Activity indicator Network Status indicator PointBus Status indicator System Power indicator Adapter Power indicator Adapter Status Network Activity Network Status PointBus Status System Power Adapter Power PWR ™ conformance tested
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A Adapter Status (Continued) Status Description Recommended action Red Unrecoverable fault has occurred: - self-test failure (Flash checksum failure at power up, ramtest failure or EEPROM checksum failure at cycle power). - firmware fatal error. Replace device. Network Activity Status Description Recommended action Off No link established with Port 1 or Port 2. Verify network cabling, and correct, as needed.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 13 Network Status Status Description Recommended action Off Device not initialized. Device does not have an IP address. Apply power to device, verify IP address, and correct, as needed. Green CIP connections present. Device online and has an IP address, and CIP connections are established. None. Flashing green No CIP connections present. Device has an IP address, but no CIP connections are established. None.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A Adapter Power Status Description Recommended action Off Not active; adapter power is off. Apply adapter power. Green Power is on; 24V input is present. None. PointBus Status Status Description Recommended action Off Device is not online. - Device has not completed dup_MAC_id test. - Device not powered - check Adapter Status indicator. Apply power to device, wait for dup_MAC_id to complete, and correct, as needed.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 15 PointBus Status (Continued) Status Description Recommended action Red Unrecoverable fault has occurred: - device is bus off. 1. Make sure an I/O module is not using a MAC ID = 0. 2. Make sure all backplane modules are communicating at the proper baud rate. 3. Cycle power to device. 4. If condition persists, replace device. Link 1 or Link 2 Activity/Status Status Description Recommended action Off No link established.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A Specifications General Attribute Value Number of modules supported, maximum 63 Number of rack optimized connections 5 (for digital modules only) Number of direct connections, maximum 20 Backplane output current, maximum 0.8 A The actual number of modules can vary. Add up the requirements of the modules you want to use, for current, to make sure they do not exceed the amperage limit of 0.8 A for the 1738-AENTR.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 17 General (Continued) Attribute Value Indicators 3 red/green status indicators on CPU: - Adapter Status - Network Status (Ports 1 and 2 combined) - PointBus Status 1 green/yellow status indicator on CPU: - Network Activity (Ports 1 and 2 combined) 2 green/yellow status indicators on base: - Link 1 Activity/Status - Link 2 Activity/Status 2 green power supply status indicators on DC-DC converter: - System Power (5V DC to PointBus Out) - Adapter Power (2
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A General (Continued) Attribute Value Weight, approx. 0.33 kg (0.72 lb) Mounting type Metal panel Enclosure type rating Meets IP65/66/67/69K (when marked) (1) Refer to publication M116-CA001A-EN-P for more information. (2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 19 Environmental Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…60 °C (-4…140 °F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat): -40…85 °C (-40…185 °F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5…95% n
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A Environmental (Continued) Attribute Value EFT/B immunity IEC 61000-4-4: ±4 kV at 5 kHz on power ports ±3 kV at 5 kHz on communications ports Surge transient immunity IEC 61000-4-5: ±1 kV @ line-line (DM) and ±2 kV @ line-earth (CM) on power ports ±2 kV @ line-earth (CM) on communications ports Conducted RF immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150…80000 kHz Publication 1738-IN028B-EN-E - February 2010
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 21 Certifications Certification (when Value product is marked)(1) CE European Union 2004/108/EC EMC Directive, compliant with: EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) EN 61326-1; Meas./Control/Lab.
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A Notes: Publication 1738-IN028B-EN-E - February 2010
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 23 Notes: Publication 1738-IN028B-EN-E - February 2010
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.