Rockwell Automation Publication 1738-UM005A-EN-P - July 2013 51
Chapter
5
Configure the Adapter for Direct Connection
and Rack Optimization in RSLogix 5000
Software
Overview
.This chapter guides you through the steps required to configure your
1738 ArmorPOINT I/O Ethernet Adapter for both direct connection and rack
optimization using RSLogix 5000 software.
It is possible to mix communication formats for different I/O modules
communicating through the same adapter. I/O modules set up to use rack
optimization communicate at the rate of the RPI configured for the
1738-AENT/B adapter. I/O modules configured for direct communication
communicate at their own set RPIs and ignore the 1738-AENT/B adapter’s RPI.
Note that the modules presented in this chapter are configured using RSLogix
5000 software, version 17. The chapter contains the following main sections
.
Topic Page
Set Up the Hardware
52
Create the Example Application 53
Configure the I/O Modules 54
Add the Local EtherNet/IP Bridge to the I/O Configuration 54
Add the ArmorPOINT I/O Adapter to the I/O Configuration 57
Add the ArmorPoint Digital Modules and Configure For Rack Optimization
Connection
61
Add the ArmorPoint Analog Modules and Configure For Direct Connection 65
Add the Digital Input Module 61
Add The Digital Output Module 63
Add the ArmorPoint Analog Modules and Configure For Direct Connection 65
Add the Analog Current Input Module 65
Add the Analog Current Output Module 67
Download the Program to the Controller 71
Verify the Module Chassis Size 72
An Overloaded 1738-AENT/B Adapter 74
Access Module Data via the 1738-AENT/B Adapter 75