Installation Instructions ArmorPoint ControlNet Adapter, Series A Catalog Number 1738-ACNR The ArmorPoint ControlNet adapter ships with the adapter and a terminating base to be used with the last I/O module on the backplane. The sealed IP67 housing of the adapter requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) ControlNet connectors are two redundant TNC style network connectors and one mini style power connector.
ArmorPoint ControlNet Adapter, Series A Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
ArmorPoint ControlNet Adapter, Series A ATTENTION 3 Environment and Enclosure This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
ArmorPoint ControlNet Adapter, Series A ATTENTION Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment.
ArmorPoint ControlNet Adapter, Series A 5 Configure Autobaud The adapter cannot reconfigure an I/O module that you previously configured to operate at a fixed baud rate. When you reuse a ArmorPoint I/O module from another ArmorPoint I/O system, configure the module to autobaud before using it with the adapter. For More Information Refer to the ArmorPoint I/O ControlNet Adapter Release Notes, publication 1738-RN001, online at URL http://literature.rockwellautomation.com.
ArmorPoint ControlNet Adapter, Series A 5. Mount the terminating base that was shipped with the adapter as the last base in the backplane instead of the base that was shipped with the I/O module. Terminating base Mounting hole Ground connection 43787 Latching mechanism Set the Node Address To set the node address, adjust the switches on the front of the module (refer to the illustration on page 1). Use a small blade screwdriver to rotate the switches.
ArmorPoint ControlNet Adapter, Series A Wire the ControlNet Adapter 7 Following are wiring instructions for the ArmorPoint ControlNet adapter. TNC Cables • Connect TNC cables to Channel A or B for single media. • Connect TNC cables to Channel A and B for redundant media.
ArmorPoint ControlNet Adapter, Series A Troubleshoot with the Indicators ControlNet A 1738-ACNR ControlNet B X10 X1 Adapter Status Indicator PointBus Status Indicator Adapter Status PontBus Status ControlNet A Status Indicator ControlNet B Status Indicator System Power Indicator Adapter Power Indicator ControlNet A Status ControlNet B Status System Power Adapter Power PWR 43792 Indication Indication Probable Cause Adapter Status Off No power applied to device.
ArmorPoint ControlNet Adapter, Series A Indication Indication Probable Cause PointBus Status Off Device is not powered - check module status indicator. Alternating Red/Green LED powerup test. Flashing Red Recoverable fault has occurred: - at power up the number of expected modules does not equal the number of modules present - a module is missing - node fault (I/O connection timeout). Red Unrecoverable fault has occurred: - the adapter is bus off - the adapter has failed its dup_MAC_ID check.
ArmorPoint ControlNet Adapter, Series A Specifications ArmorPoint Control Adapter - 1738-ACNR Expansion I/O Capacity Following are specifications for the 1738 ArmorPoint ControlNet adapter. • Maximum of 63 modules • Maximum of 5 Rack Optimized connections (for digital modules only) • Maximum of 25 Direct connections • 1738-ACNR backplane current output = 1.0A maximum.
ArmorPoint ControlNet Adapter, Series A Power Supply Specifications Power Supply Input Voltage Rating Inrush Current Field Side Power Requirements, Maximum Interruption General Specifications LED Indicators Power Consumption, Maximum Power Dissipation, Maximum Thermal Dissipation, Maximum PointBus Output Current, Maximum Input Overvoltage Protection Isolation Voltage (continuous-voltage withstand rating) Field Power Bus Nominal Voltage Supply Voltage Supply Current Dimensions Inches (Millimeters) Ope
ArmorPoint ControlNet Adapter, Series A General Specifications (continued) Radiated RF Immunity IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz EFT/B Immunity IEC 61000-4-4: ±4kV at 5kHz on power ports ±3kV at 5kHz on signal ports Surge Transient Immunity IEC 61000-4-5: ±1kV line-line(DM) and ±2kV line-earth(CM) on power ports ±2kV line-earth(CM) on shielded ports Conducted RF Immunity IEC 610
ArmorPoint ControlNet Adapter, Series A 13 Notes: Publication 1738-IN016B-EN-E - March 2005
Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.