Manual
ArmorPoint I/O Modules with 8 Configurable 24V DC Points and DeviceLogix 11
Publication
1738-IN027B-EN-E - February 2010
You can select other produced assemblies:
• Produced assembly instance 4 is the first byte of produced assembly
instance 101 (Data [0]).
• Produced assembly instance 111 is the first eight bytes of produced
assembly instance 101 (Data [0]…[7]).
In RSLogix5000, the default tags will be:
• AdapterName:SlotNumber:I.Data
• AdapterName:SlotNumber:I.LogicDefinedData
• AdapterName:SlotNumber:I.Status.LogicEnabled
• AdapterName:SlotNumber:I.Status.Owned
• AdapterName:SlotNumber:I.PeerMissing
• AdapterName:SlotNumber:I.LogicDefinedIntData[0...7]
Default Data Map - Consumed Assembly Instance 102
Message Size: 20 Bytes
Bit 76543210
Data [0] Pt 07 PT 06 Pt 05 Pt 04 Pt 03 Pt 02 Pt 01 Pt 00
Data [1] CNB 07 CNB 06 CNB 05 CNB 04 CNB 03 CNB 02 CNB 01 CNB 00
Data [2] Reserved
Data [3]
Data [4] Consume Network Analog Word 0
Data [5]
Data [6] Consume Network Analog Word 1
Data [7]
Data [8] Consume Network Analog Word 2
Data [9]
Data [10] Consume Network Analog Word 3
Data [11]