User Manual
Publication 1738-IN010A-EN-E - June 2004
ArmorPoint I/O RS-485 ASCII Module, Series A 11
Send (Produce) on DeviceNet to Master
Receive String Data Type Array, short_string, string
Pad Mode Pad mode disabled, enabled
Pad Character ASCII character
Receive Swap Mode Disabled, 16-bit, 24-bit, 32-bit swap
DeviceNet Handshake Mode Master/slave handshake, produce immediate
Produce Assembly Size 4-132
Serial Data 0-128 bytes
Receive Transaction ID 0-255
Serial Port Transmit to ASCII Device
Maximum Number of Transmit Characters 1-128
Transmit End Delimiter Mode No, exclude, include end delimiter
Transmit End Delimiter Character ASCII
Consume on DeviceNet from Master
Consume String Data Type Array, short_string, string
Transmit Swap Mode Disabled, 16-bit, 24-bit, 32-bit swap
DeviceNet Record Header Mode Transmit handshake/immediate
Consume Assembly Size 4-132
Serial Port Transmit/Explicit Messages
Transmit Serial Data String 0-128 bytes
Transmitted Serial Data Length 0-128 bytes
Transmit Transaction ID 0-255
Status TX FIFO overflow, RX FIFO overflow, RX parity error, handshake error, new data flag
General Specifications
Dimensions Inches (Metric) 1.25H x 2.63W x 4.25D (31.75H x 66.80W x 107.95D)
Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5-95% non-condensing
Shock IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g
Vibration IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
ESD Immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B Immunity IEC 61000-4-4:
±2kV at 5kHz on communications ports