Visualization Chapter 5
When all the Add-On Instructions are in the routine, connect them as shown
below. Each I_AB56IFxH_Chan connects to one of P_AIn56H.
Configure I_AB56IF8H
Make the following modifications to each I_AB56IF8H Add-On Instruction.
• You must create the backing tag and all of the reference input tags. Follow a
system or naming convention for your application to keep multiple
instances of this Add-On Instruction organized.
• Configure the Ref_Inp tag to point to the location of the Analog HART
Interface module in the chassis.