User Manual Owner's manual

Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014 13
Chapter 1
Installation
Connect a 2-Wire Field
Instrument
HART communication is active only with current inputs. Connect a 2-wire field
instrument to any channel of the HART input module in a 2-wire configuration
for current input.
HART devices that support 2-wire connections include the following.
Topic Page
Connect a 2-Wire Field Instrument 13
Connect a 4-Wire Field Instrument 17
Device See appendix
Prowirl 73 flowmeter Appendix D on page 97
Levelflex M guided level-radar Appendix F on page 109
Micropilot M level-radar Appendix G on page 115
Prosonic M ultrasonic level Appendix E on page 103
Liquiline M CM42 transmitter Appendix M on page 147
Cerabar S pressure transmitter Appendix H on page 119
Deltabar S differential pressure Appendix I on page 125
iTEMP TMT162 temperature transmitter Appendix K on page 139
iTEMP TMT182 temperature transmitter Appendix L on page 143