User Manual Instruction Manual
Publication 1734-UM003B-EN-P - August 2005
A-8 Configure Modules in RSLogix 5000 Software
9. For Time Base, select a value between 10 and 3000 milliseconds,
in multiples of 10, referring to the table.
10. Note that the value for Actual Gate Interval that appears when
counter type is Rate Measurement and shows the product of
Gate Multiplier and Time Base below 3 seconds (3000
milliseconds).
11. For Filter, select the Frequency, which is the value you use to
filter A/B/Z/ inputs when you check the checkboxes.
The frequency default and selections are the following.
• Default is 50 Hz.
• Selections for Filter include these.
- No Filter
- 50 kHz
- 5 kHz
- 500 Hz
- 50 Hz
12. Check the checkboxes for the following, which use the value
you selected for Filter.
• Filter A
• Filter B
• Filter Z
13. For Invert Input Z, check the checkbox to invert the signal at Z
input.
Selections for Period/Rate and Rate Measurement
For This Value Default Is: Select
Frequency Precision X 1 X 0.0001
X 0.001
X 0.01
X 0.1
X 1
X 10
X 100
Gate Multiplier 1 1 to 200
Time Base 1000 10 to 3000 in multiples of 10