Safety Modules User Manual Owner's manual

80 Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 5 Configure the Module in a GuardLogix Controller System
e. From the Input Data pull-down menu, choose Safety or None.
f. From the Output Data pull-down menu, choose from the following
options.
Choose Description
Safety These tags are created for the target module:
RunMode for module mode
ConnectionFaulted for communication status
Safety Data for safety inputs from the module
Choose Description
None Results in an input only connection to the module. Inputs and status are read, but no
outputs are written. You can still use the test outputs as pulse test outputs or a power
supply. If you are not controlling the module’s test outputs via application logic, this is
the recommended setting.
Test
(1)
(1) To have this choice from the pull-down menu, you must choose ‘This Controller’ from the Configured By pull-down
menu.
Creates these tags to enable application logic control of the test outputs on the module.
This selection allows the test outputs to be used as standard outputs and muting
outputs.
IMPORTANT
When test outputs are configured as standard outputs, they
must not be used for safety purposes.