Environmental Specifications
Power bus, operating voltage range 19.2…28.8V DC, Class 2
Power bus current (no load), max 50 mA
Input filter time, OFF to ON
(4)
0…126 ms (in 6 ms increments)
Input filter time, ON to OFF
(4)
Terminal base screw torque See terminal base specifications
Indicators 1 yellow lock status indicator
1 green/yellow power status indicator
8 I/O channel status indicators
Keyswitch positions (left and right) Key 1 = 8 (left); Key 2 = 2 (right)
Pilot duty rating Not rated
North America temp code T4
IEC temp code T4
Enclosure type rating None (open-style)
Wiring category
(5)
2 - on signal ports
Wire size Determined by installed terminal block
Weight, approx. 62.4 g (2.2 oz)
Dimensions (HxWxD), approx. (without terminal block) 77 x 25 x 55 mm (3.03 x 0.98 x 2.17 in.)
(1) To comply with UL certification requirements, field power must be supplied from a single Class 2‐compliant power supply
(See Choosing a Power Supply
on page 45) which limits available field power to 100VA. Therefore, the aggregate current of outputs
per module is limited to a maximum set by the 100VA limit (unless derated further as shown) for applications that require UL
listing.
(2) Maximum power dissipation applies when using 28.8V DC module supply and maximum power dissipated with all eight outputs in
the ON state.
(3) Typical power dissipation applies when using 24V DC module supply and nominal power dissipated with all eight outputs in the ON
state.
(4) Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off time is the time from a
valid input signal to recognition by the module.
(5) Use this conductor category information for planning conductor routing. Refer to the Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
.
Attribute 1734-OB8S Series B
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)
(1)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Temperature, surrounding air, max 55 °C (131 °F)
(1)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC 60068-2-6, (Test Fc, Operating)
5 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g
Corrosives 1734-IB8S and 1734-OB8S Series B only: G2 (ISA S71.04)