Safety Modules User Manual Owner's manual
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014 117
Configure the Module for a SmartGuard Controller Chapter 6
5. Double-click each Engineering Units Alarms group to display parameters
for editing.
Parameter Name Value Description Default
High High/Low Low Alarm
Enable
Disable Enable or disable alarms.
Disable
Enable
High High Alarm -32768…32767 Follow these guidelines when setting the alarm values.
• The High High alarm value must be greater than or equal to the High alarm value.
• The High alarm value must be greater that the Low alarm value.
• The Low Low alarm value must be less than or equal to the Low alarm value.
• These values are based on the Engineering units
32767
Low Low Alarm -32768…32767 0
High Alarm -32768…32767 32767
Low Alarm -32768…32767 0
High High/Low Low Alarm
Deadband
0…32767 Deadband on the High High and Low Low alarms. 0
High/Low Alarm Deadband 0…32767 Deadband on the High and Low alarms. 0