Manual
POINT I/O 120/240V ac Expansion Power Supply 15
Publication
1734-IN017A-EN-P - December 2005
ESD Immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz
10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
EFT/B Immunity IEC 61000-4-4:
±4 kV at 5 kHz on power ports
Surge Transient Immunity IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
Conducted RF Immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz
Emissions CISPR 11
Group 1, Class A
Enclosure Type Rating None (open-style)
Voltage Variation 30% dips for 1 period at 0 ° & 180 ° on ac supply ports
60% dips for 5 and 50 periods on ac supply ports
±10% fluctuations for 15 minutes on ac supply ports
>95% interruptions for 250 periods on ac supply ports
Conductors Wire Size
Category
14…22 AWG (2.5…0.34 mm
2
) - solid or stranded copper wire
rated at 75 °C or greater
1.2 mm (3/64 inch) insulation maximum
1
(1)
on power ports
Terminal Base Screw Torque 0.8 Nm (7 lb-in)
Field Wiring Terminations 0 - No Connection 1 - No Connection
2 - Protective Earth Ground 3 - Protective Earth Ground
4 - L2/N 5 - L2/N
6 - L1 7 - L1
Weight Metric
Imperial
182 g
6.40 oz