Instruction Manual

Publication 1734-UM005B-EN-P - June 2001
B-14 Default Data Maps
1734-OE2V Analog Voltage
Output Module
Product Code: 0019h
Data Map:
Output size: 2 Word; Input size: 0 Word
Configuration Data:
Diagnostic Data
Possible Error Codes:
7654321 0
Produces (Rx) Output Channel 0
Output Channel 1
Consumes (Tx) No consumed data
7 654321 0
Reserved AD R IA FA
Engineering Units Low (high byte) Default value = 06h
Engineering Units Low (low byte) Default value = 66h
Engineering Units High (high byte) Default value = 1Fh
Engineering Units High (low byte) Default value = FFh
Fault Value (high byte) Default value = 00
Fault Value (low byte) Default value = 00
Idle Value (high byte) Default value = 00
Idle Value (low byte) Default value = 00
Meaning of bits described below
FA = Fault Action IA = Idle Value
Value Definition Value Definition
0 Hold Last State 0 Hold Last State
1 Fault Value (default) 1 Idle Value (default)
R = Range AD = Alarm Disable
Value Definition Value Definition
0 -10 to +10V (default) 0 Enable (default)
1 0 to +10V 1 Disable
Code Error Type
6 Wire Break
16 Module incorrect or missing. Reported on channel 0, applies to whole module.