Instruction Manual

Publication 1734-UM005B-EN-P - June 2001
B-12 Default Data Maps
1734-IE2V Analog Voltage
Input Module
Product Code: 0018h
Data Map:
Output size: 0 Words; Input size: 2 Words
Configuration Data:
7654321 0
Produces (Rx) Input Channel 0
Input Channel 1
Consumes (Tx) No consumed data
7 654321 0
Reserved DF AD R Notch Filter NF
Engineering Units Low (high byte) Default value = 06h
Engineering Units Low (low byte) Default value = 66h
Engineering Units High (high byte) Default value = 3Fh
Engineering Units High (low byte) Default value = FFh
Low Alarm Threshold (high byte) Default value = 0Ch
Low Alarm Threshold (low byte) Default value = 29h
High Alarm Threshold (high byte) Default value =40h
High Alarm Threshold (low byte) Default value = A3h
Meaning of bits described below
NF = Notch Filter Values
Value Definition
00 50Hz
01 60Hz (default)
10 250Hz
11 500Hz
AD = Alarm Disable R = Range
Value Definition Value Definition
0 Enable (default) 0 -10 to +10V (default)
1 Disable 1 0 to +10V