Installation Instructions Owner manual
14 POINT I/O PROFIBUS Adapter
Publication 1734-IN014C-EN-P - March 2002
ESD Immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from
30MHz to 1000MHz
10V/m with 200Hz 50% pulse 100%AM at
900MHz
EFT/B Immunity IEC61000-4-4
±4kV at 2.5kHz on power ports
±4kV at 2.5kHz on communications ports
Surge Transient Immunity IEC 61000-4-5:
±500V line-line(DM) and ±500V line-earth(CM)
on dc power ports
±4kV line-earth(CM) on shielded ports
Conducted RF Immunity IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from
150kHz to 80MHz
Emissions CISPR 11
Group 1, Class A
Enclosure Type Rating None (open-style)
Field Wiring Terminations
PROFIBUS 1 - Not connected 6 - +5V Bus
2 - Not connected 7 - Not connected
3 - +RTX/TX data line 8 - Negative RTX/TX
4 - Request to send 9 - Not connected
5 - Ground Bus Housing - Earth ground
Power Supply 0 - No Connection 1 - No Connection
2 - Chassis Ground 3 - Chassis Ground
4 - Common 5 - Common
6 - Supply 7 - Supply
Conductors Wire Size
Category
14 AWG (2.5mm
2
) - 22 AWG (0.25mm
2
) solid or
stranded copper wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
2
1
Terminal Base Screw Torque 7 pound-inches (0.6Nm)
Mass 9.0 oz/255 grams