Installation Instructions Owner manual

13 POINT I/O PROFIBUS Adapter
Publication 1734-IN014C-EN-P - March 2002
Interruption Output voltage will stay within specifications
when input drops out for 10ms at 10V with
maximum load.
General Specifications
Indicators 3 red/green status indicators
Adapter status
PROFIBUS status
PointBus status
2 green power supply status indicators:
System Power (PointBus 5V power)
Field Power (24V from field supply)
Power Consumption 8.1W maximum @ 28.8V dc
Power Dissipation 2.8W maximum @ 28.8V
Thermal Dissipation 9.5 BTU/hr maximum @ 28.8V dc
Isolation Voltage 1250V rms/V ac
Field Power Bus
Nominal Voltage
Supply Voltage Range
Supply Current
24V dc
10-28.8V dc range,
10A maximum
Dimensions Inches
(Millimeters)
3.0H x 2.16W x 5.25L
(76.2H x 54.9W x 133.4L)
Environmental Conditions
Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock):
-20 to 55°C (-4 to 131°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock):
-40 to 85°C (-40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged
Nonoperating
Damp Heat):
5 to 95% noncondensing
Shock
Operating
Non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30g peak acceleration
50g peak acceleration
Vibration IEC 60068-2-6, (Test Fc, Operating)
Tested 5g @ 10-500Hz