Chapter 6 Interlocking and Data Transfer between Controllers
Configure a MSG to an SLC 500 Controller
Configure a MSG to a PLC-5 Controller
3. Click the Communication tab.
4. In the Path field, type the communication path.
If the data is And you want to For this item Type or choose
Integer Read (receive) data Message Type SLC Typed Read
Source Element Data table address in the SLC 500 controller (for example, N7:10)
Number of Elements Number of integers to transfer
Destination Tag First element of int_buffer
Write (send) data Message Type SLC Typed Write
Source Tag First Element of int_buffer
Number of Elements Number of integers to transfer
Destination Element Data table address in the SLC 500 controller (for example, N7:10)
Floating-point (REAL) Read (receive) data Message Type SLC Typed Read
Source Element Data table address in the SLC 500 controller (for example, F8:0)
Number of Elements Number of values to transfer
Destination Tag First element of the tag (controller-scoped) in this controller for the data
Write (send) data Message Type SLC Typed Write
Source Tag First element of the tag (controller-scoped) in this controller that contains the data
Number of Elements Number of values to transfer
Destination Element Data table address in the SLC 500 controller (for example, F8:0)
If the data is And you want to For this item Type or choose
Integer Read (receive) data Message Type PLC5 Typed Read
Source Element Data table address in the PLC-5 controller (for example, N7:10)
Number of Elements Number of integers to transfer
Destination Tag First element of int_buffer
Write (send) data Message Type PLC5 Typed Write
Source Tag First element of int_buffer
Number of Elements Number of integers to transfer
Destination Element Data Table address in the PLC-5 controller (for example, N7:10)
Floating-point (REAL) Read (receive) data Message Type PLC5 Typed Read
Source Element Data table address in the PLC-5 controller (for example, F8:0)
Number of Elements Number of values to transfer
Destination Tag First element of the tag (controller-scoped) in this controller for the data
Write (send) data Message Type PLC5 Typed Write
Source Tag First element of the tag (controller-scoped) in this controller that contains the data
Number of Elements Number of values to transfer
Destination Element Data table address in the PLC-5 controller (for example, F8:0)