Configuration User Manual

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014 119
Diagnostic Web Pages Chapter 9
The Ethernet Statistics diagnostic web page presents a summary of the status of
communication activity on the Ethernet network.
The most commonly monitored fields are described in
Table 30 on page 119.
Table 30 - Ethernet Statistics Web Page
Field Specifies
Ethernet Port 1 (These definitions apply to the same fields in the Ethernet Port 2 section.)
Interface State Whether the port is turned off or on. Active or inactive indicates whether there is a cable connected.
Link Status Whether the port is blocked for DLR protocol frames.
Speed Whether the Ethernet port is operating at 10 or 100 MBps.
Duplex Whether the Ethernet port is operating at half duplex or full duplex.
Autonegotiate Status Whether the port speed and Duplex mode were determined via autonegotiation or whether they were manually
configured.