User Manual Manual
Publication 1734-UM008B-EN-P - August 2005
1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-5
Filter Time Note
To enter Filter values from +32,768 to +65,535 µs, use this conversion
formula:
Desired Filter Value (in µs) - 65536 = Entered Filter Value (in
µs).
Example: For a 40ms filter time, 40000 - 65536 = -25536
Discrete 2 POINT Output –
Without Diagnostic Status
1734-OA2
2 POINT 120V AC Output
1734-OW2
2 POINT AC/DC Relay Output
1734-OX2
2 POINT Relay Output N.O./N.C.
Configuration Data Data Type Default
Value
Valid Data Values
Fault Mode - POINT 0, 1 SINT, BIT 0 0=Fault Value
1=Hold Last State
Fault Value - POINT 0, 1 SINT, BIT 0 0=Off
1=On
Program Mode - POINT 0, 1 SINT, BIT 0 0=Program Value
1=Hold Last State
Program Value - POINT 0, 1 SINT, BIT 0 0=Off
1=On
Input Data Data Type Default
Value
Valid Data Values
None
Output Data Data Type Default
Value
Valid Data Values
Output Data - POINT 0, 1 SINT, BIT 0 0=Off
1=On