User Manual Manual
Publication 1734-UM008B-EN-P - August 2005
4-12 Configure the Adapter
• Connection
• Module Info
• Fault/Program Action
• Configuration
For details on completing entries for Fault/Program Action and
Configuration, refer to online help or the user manual for your
individual module.
11. Choose Connection to see this Module Properties dialog.
12. Uncheck the following checkboxes, if checked.
• Inhibit Module
• Major Fault On Controller If Connection Fails While in Run
Mode
13. Enter RPI for direct connections.
If you are configuring a digital module and chose direct
connections, the I/O module RPI is selectable. RPI is not
selectable if you chose rack optimizated communication.
Module Type Default Time
Analog 80 ms
Digital 20 ms
Specialty 80 ms