Instruction Manual
16 POINT I/O Module with 8 Configurable 24V DC Points
Publication
1734-IN038A-EN-P - October 2008
In RSLogix5000, the default tags will be:
• AdapterName:SlotNumber:C.FilterOffOn
• AdapterName:SlotNumber:C.FilterOnOff
• AdapterName:SlotNumber:C.PtPointNumberFaultMode
• AdapterName:SlotNumber:C.PtPointNumberFaultValue
• AdapterName:SlotNumber:C.PtPointNumberProgMode
• AdapterName:SlotNumber:C.PtPointNumberProgValue
Default Data Map - Configuration Assembly Instance 103
Message Size: 8 Bytes
76543210
Data [0] Group Off2On Input filter
Data [1]
Data [2] Group On2Off Input filter
Data [3]
Data [4] FltM 7 FltM 6 FltM 5 FltM 4 FltM 3 FltM 2 FltM 1 FltM 0
Data [5] FltV 7 FltV 6 FltV 5 FltV 4 FltV 3 FltV 2 FltV 1 FltV 0
Data [6] IdlM 7 IdlM 6 IdlM 5 IdlM 4 IdlM 3 IdlM 2 IdlM 1 IdlM 0
Data [7] IdlV 7 IdlV 6 IdlV 5 IdlV 4IdlV 3IdlV 2IdlV 1IdlV 0
Where:
Filter = 0 to 65000 ms (0 = default)
Filter = 0 to 65535 ms (1000 = default)
FltM = Fault Mode (0 = Fault Value (default), 1 = Hold Last State)
FltV = Fault Value (0 = OFF (default), 1 = ON)
IdlM = Idle Mode (0 = Idle Value (default), 1 = Hold Last State)
IdlV = Idle Value (0 = OFF (default), 1 = ON)