Installation Instructions Owner manual
POINT I/O RS-232 and RS-485 ASCII Modules 19
Publication
1734-IN588B-EN-P - July 2003
Specifications - 1734-232ASC, -485ASC Modules (Continued)
General Specifications
Dimensions Inches
(Millimeters)
2.21H x 0.47W x 2.97L
(56H x 12W x 75.5L)
Environmental Conditions
Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 55°C (-4 to 131°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock): -40 to 85
°C (-40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating
Damp Heat): 5 to 95% noncondensing
Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Operating 30g peak acceleration
Nonoperating 50g peak acceleration
Vibration IEC 60068-2-6 (Test Fc, Operating)
5g @ 10-500Hz
ESD Immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
2000MHz
10V/m with 200Hz 50% pulse 100%AM from 900MHz
EFT/B Immunity IEC 61000-4-4:
+4kV at 2.5kHz on power ports
+2kV at 5kHz on signal ports
Surge Transient Immunity IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on power
ports
+2kV line-earth (CM) on shielded ports