Specifications - 1734-232ASC, -485ASC Modules (Continued)
Send (Produce) on DeviceNet to Master
Receive String Data Type Array, short_string, string
Pad Mode Pad mode disabled, enabled
Pad Character ASCII character
Receive Swap Mode Disabled, 16-bit, 24-bit, 32-bit swap
DeviceNet Handshake Mode Master/slave handshake, produce immediate
Produce Assembly Size 4-132
Serial Data 0-128 bytes
Receive Transaction ID 0-255
Serial Port Transmit to ASCII Device
Max Number of Transmit Chars 1-128
Transmit End Delimiter Mode No, exclude, include end delimiter
Transmit End Delimiter Character ASCII character
Consume on DeviceNet from Master
Consume String Data Type Array, short_string, string
Transmit Swap Mode Disabled, 16-bit, 24-bit, 32-bit swap
DeviceNet Record Header Mode Transmit handshake/immediate
Consume Assembly Size 4-132
Serial Port Transmit/Explicit Messages
Transmit Serial Data String 0-128 bytes
Transmitted Serial Data Length 0-128 bytes
Transmit Transaction ID 0-255
Status TX FIFO overflow, RX FIFO overflow, RX parity error,
handshake error, new data flag