Installation Instructions ArmorBlock 16-Point EtherNet/IP Module, Series A Catalog Numbers 1732E-IB16M12, 1732E-OB16M12, 1732E-16CFGM12, 1732E-16CFGM12W, 1732E-IB16M12W Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 3 About the EtherNet/IP ArmorBlock 16-Point I/O Modules 4 Catalog Number Explanation 6 Install the Module 6 Set the Network Address 6 Mount the Module 7 Product Dimensions 8 Connect the I/O, Network and Auxiliary Cables
ArmorBlock 16-Point EtherNet/IP Module, Series A Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
ArmorBlock 16-Point EtherNet/IP Module, Series A 3 Environment and Enclosure Follow these guidelines for environment and enclosure information for this equipment. ATTENTION This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
ArmorBlock 16-Point EtherNet/IP Module, Series A About the EtherNet/IP ArmorBlock 16-Point I/O Modules The EtherNet/IP 1732E ArmorBlock is a 24V DC I/O module that communicates via EtherNet/IP. The sealed IP65, IP67 and IP69K housing of these modules requires no enclosure. Note that environmental requirements other than IP65, IP67 and IP69K may require an additional appropriate enclosure. I/O connectors are sealed M12 style.
ArmorBlock 16-Point EtherNet/IP Module, Series A 5 EtherNet/IP ArmorBlock 16-Point I/O Module Functional Earth(1) EtherNet/IP D-Code M12 Connector Status LEDs Plastic Housing I/O Connectors I/O Connectors Node Address Switches Protective Earth MOD NET LINK 0 15 1 14 2 13 3 12 4 11 5 6 10 9 Metal Housing I/O Connectors 8 7 Auxiliary Power EtherNet/IP D-Code M12 Connector EtherNet/IP X10 P W R X100 X1 (2) 44231 44232 Node Address Switches Protective Earth(2) (1) Functiona
ArmorBlock 16-Point EtherNet/IP Module, Series A Catalog Number Explanation Refer to the table for a description of the catalog numbers. Cat. No.
ArmorBlock 16-Point EtherNet/IP Module, Series A 7 of the module. Use a small blade screwdriver to rotate the switches. Line up the small notch on the switch with the number setting you wish to use. Valid settings range from 001...254. Network Address Example This example shows the network address set at 163. 44233 When the switches are set to a valid number, the I/O block’s IP address is 192.168.1.xxx (where xxx represents the number set on the switches). The I/O block’s subnet mask is 255.255.255.
ArmorBlock 16-Point EtherNet/IP Module, Series A Product Dimensions Refer to the mounting dimensions illustration to help you mount the modules. 65 mm (2.56 in.) 43.25 mm (1.70 in.) 26.5 mm (1.04 in.) 0 15 1 14 2 13 3 4 12 11 5 6 10 9 179 mm (7.05 in.) 169 mm (6.64 in.) 8 7 P W R 44234 Front View Side View Mount the Module in High Vibration Areas If you mount the module in an area that is subject to shock or vibration, we recommend you use a flat and a lock washer to mount the module.
ArmorBlock 16-Point EtherNet/IP Module, Series A 9 High Vibration Area Mounting Lock Washer Flat Washer 44235 Connect the I/O, Network and Auxiliary Cables to the ArmorBlock Module The ArmorBlock EtherNet/IP family has 5-pin micro-style connectors. We provide caps to cover the unused connectors on your module. Connect the quick-disconnect cord sets you selected for your module to the appropriate ports.
ArmorBlock 16-Point EtherNet/IP Module, Series A Network Connectors Refer to the pinout diagrams for the network connectors. D-Code M12 Female Network Connector (View into Connector) Pin 1 M12_Tx+ Pin 2 M12_Rx+ Pin 3 M12_TxPin 4 M12_RxPin 5 Connector Shell Shield GND 4 1 3 2 5 44236 IMPORTANT Use the 1585D–M4DC–H: Polyamide small body unshielded or the 1585D–M4DC–SH: Zinc die-cast large body shielded mating connectors for the D-Code M12 female network connector.
ArmorBlock 16-Point EtherNet/IP Module, Series A 11 I/O Connectors Refer to the pinout diagrams for the I/O connectors.
ArmorBlock 16-Point EtherNet/IP Module, Series A • If an I/O point is to be an input, wire the input device as normal and leave the associated output de-energized at all times. I/O Self-configure Circuitry Turn output on Output circuit From PLC To PLC Sensor or actuator Output scan list Input scan list Input is on (or output is on) Input circuit Connector pin 43601 Refer to the illustration for configuration operations.
ArmorBlock 16-Point EtherNet/IP Module, Series A 13 The module is 24V DC Sink In/Source Out: • 16 Input • 16 Output • 16 Input Or Output points or any mix of 16 (for example, 15 + 1; 8 +8) The output is short circuit protected and output monitoring in “Self-configuring” style. Refer to On-Machine Connectivity Catalog, publication M117-CA001, for Rockwell Automation cable and cord set offerings or access the Connection Systems website at http://www.ab.com/connectionsystems/.
ArmorBlock 16-Point EtherNet/IP Module, Series A Mini-style 4-Pin Female Connector (from power cable) 2 4 1 3 (View into Connector) Pin 1 Output Power+ Pin 2 Sensor/MDL Power+ Pin 3 Sensor/MDL PowerPin 4 Output Power44237 Mini-style 4-Pin Male Receptacle (on the ArmorBlock) 4 2 3 1 (View into Receptacle) Pin 1 Output Power+ Pin 2 Sensor/MDL Power+ Pin 3 Sensor/MDL PowerPin 4 Output Power44238 Auxiliary power is based on a 4-pin connector system and is used to provide 24V DC power to I/O modul
ArmorBlock 16-Point EtherNet/IP Module, Series A 15 Interpret the LED Indicators This module has the following indicators: • Network, Module, and Link status indicators for EtherNet/IP • Auxiliary Power indicator • Individual I/O status indicators for inputs and outputs.
ArmorBlock 16-Point EtherNet/IP Module, Series A ArmorBlock Link status indicator Module status indicator Network status indicator I/O status indicators I/O status indicators Auxiliary power status indicator 44231 Network Status Indicator – NET State Status Description Recommended Action Off Not online The device is not initialized or the module does not have an IP address. Wait until the module has completed initialization or assign an IP address.
ArmorBlock 16-Point EtherNet/IP Module, Series A 17 State Status Description Recommended Action Flashing red Connection time out One or more connections have timed out. Reset connections to the module. Red Duplicate IP The module has detected that its IP address is already in use. Resolve the IP address conflict. Flashing red/green Self-test in progress The module is performing a powerup self-test.
ArmorBlock 16-Point EtherNet/IP Module, Series A IMPORTANT The Module Status LED indicator remains solid red for a maximum of 30 s while the module completes its POST (Power-On Self Test). Network Link Status Indicator – LINK State Status Description Recommended Action Off No network link There is no network link established. Establish a network link. Flashing green/off Network link active There is transmitting or receiving activity to the module.
ArmorBlock 16-Point EtherNet/IP Module, Series A 19 Specifications ArmorBlock 2-Port EtherNet/IP Module – 1732E-IB16M12x, 1732E-16CFGM12x Attributes Value Number of inputs 16 Input type Sink, 24V DC Voltage, off-state input, max 5V DC Voltage, on-state input, max 30V DC Voltage, on-state input, nom 24V DC Voltage, on-state input, min 11V DC Voltage, sensor source, max 30V Voltage, sensor source, min 11V Current, off-state input, max 1.
ArmorBlock 16-Point EtherNet/IP Module, Series A ArmorBlock 2-Port EtherNet/IP Module – 1732E-16CFGM12x, 1732E-OB16M12 Current on-state output, max 0.5 A – 1732E-16CFGM12x 2 A – 1732E-OB16M12 Current per module, max 8.0 A (all outputs) Leakage current, off-state output, max 50 μA Surge current per output, max 3.
ArmorBlock 16-Point EtherNet/IP Module, Series A 21 General Specifications Attribute Value Dimensions (HxWxD), approx. 179 x 65 x 43.25 mm (7.05 x 2.56 x 1.70 in.) Weight, approx. 0.34 kg (0.75 lb) Enclosure type rating Meets IP65/66/67/69K (when marked), and NEMA 4X/6P with receptacle dust caps or cable termination.
ArmorBlock 16-Point EtherNet/IP Module, Series A Environmental Specifications Attribute Value Vibration IEC60068-2-6 (Test Fc, Operating): 5 g @ 10…500 Hz Shock, operating IEC60068-2-27 (Test Ea, Unpackaged Shock): 30 g Shock, non-operating IEC60068-2-27 (Test Ea, Unpackaged Shock): 50 g Emissions CISPR 11: Group 1, Class A ESD immunity IEC 61000-4-2: 8 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...
ArmorBlock 16-Point EtherNet/IP Module, Series A 23 Certifications Certification (when Value product is marked)(1) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657. CE European Union 89/336/EEC EMC Directive, compliant with: EN 61326; Meas./Control/Lab.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.