Installation Instructions 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Catalog Numbers 1732E-IF4M12R, 1732E-OF4M12R Table of Contents Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 Overview 4 Catalog Number Explanation 6 Install the Module 6 Set the Network Address 6 Mount the Module 8 Product Dimensions 8 Connect the I/O, Network and Auxiliary Cables to the Module 10 Configure the Module 14
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 3 Environment and Enclosure ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Additional Resources Resource Description 1732E ArmorBlock™ Dual-Port EtherNet/IP 4-Point Analog Modules Wiring Diagrams 1732E-WD003 Pinout guide wiring diagram for the ArmorBlock dual-port EtherNet/IP 4-Point Analog modules (1732E-IF4M12R, 1732E-OF4M12R, 1732E-IT4IM12R, 1732E-IR4IM12R).
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 5 Module Identification Function earth(1) EtherNet/IP D-code M12 connector Link 1 status indicator Module status indicator EtherNet/IP D-code M12 connector Link 2 status indicator Network status indicator Node address switches I/O status indicators M12 style I/O connectors Auxiliary Power status indicator Micro-style power in Micro-style power out 45871 (1) Function Earth grounds the I/O block’s EtherNet/IP communicatio
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Optional Accessory The following table identifies optional accessory that you can use with the modules that have to be ordered separately. Option Catalog Number Snap-in individual marker card(1) 1492-MD6X9 (1) Provides labelling for the terminal blocks to allow for easy identification and description. Catalog Number Explanation Refer to the table for a description of the module catalog numbers.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules • 7 retrieve the IP address from nonvolatile memory. The I/O block reads the switches first to determine if the switches are set to a valid number. To set the network address: 1. Remove power. 2. Remove the switch dust caps. 3. Rotate the three (3) switches on the front of the module using a small blade screwdriver. 4. Line up the small notch on the switch with the number setting you wish to use.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Network Address Switch value 001 The module IP address cannot be the same as the gateway address. If the address switches are set to 001, the module IP address becomes 192.168.1.1, which is the same as the default gateway address. In this case, the module gateway address will be set to 0.0.0.0. Default Factory Configuration The switch value 888 resets the module to default factory configuration on power up.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 9 Module Dimensions 37 (1.46) 16.2 (0.64) 19.8 (0.78) 166.5 (6.56) 179 (7.05) 168.6 (6.64) 27 (1.06) 6LGH 0RXQWLQJ 43.3 (1.70) Measurements are in millimeters (inches) 32 (1.26) 18 (0.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Mount the Module in High Vibration Areas If you mount the module in an area that is subject to shock or vibration, we recommend you use a flat and a lock washer to mount the module. Mount the flat and the lock washer as shown in the mounting illustration. Torque the mounting screws to 0.68 Nm (6 lb-in.).
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 11 Micro-style M12 5-Pin Input Female Connector – 1732E-OF4M12R 3 2 5 4 1 45868 (View into connector) Pin 1 Current Output + Pin 2 Current Common Pin 3 Voltage Output + Pin 4 Voltage Common Pin 5 No Connect Ethernet Connector D-Code Micro Network Female Connector 3 2 5 1 4 44808 IMPORTANT (View into connector 1) Pin 1 M12_Tx+ Pin 2 M12_Rx+ Pin 3 M12_TxPin 4 M12_RxPin 5 Connector shell shield GND Use the 1585D–M4DC–H:
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Use two twisted pair CAT5E UTP or STP cables.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 13 Current Mode Connections – 1732E-IF4M12R 2-wire connection Common 3 2 5 4 1 – Current Input Device + 3-wire connection 3 2 4 1 Common – 5 V DC + Current Input Device + V DC 4-wire connection 3 2 – 5 1 4 + Current Input Device V AC or V DC 46042 ATTENTION: The device does not provide bonding or grounding terminal. Customer shall provide own bonding or grounding.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Configure the Module Refer to the illustration for configuration operations.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 15 Power Connectors Attach the micro-style 4-pin connector to the micro-style 4-pin receptacle as shown below. Micro-style 4-Pin Input Male Receptacle Male Input Female Output (View into receptacle) Pin 1 Auxiliary power+ Pin 2 Module power+ Pin 3 Module powerPin 4 Auxiliary power- 2 1 3 4 2 3 1 4 45764 45763 The power required by the module is based on a 4-pin micro-style connector system.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Interpret LED Indicators This module has the following indicators: • Network, Module, and Link status indicators for EtherNet/IP • Auxiliary Power status indicator • Individual I/O status indicators for inputs/outputs Publication 1732E-IN006C-EN-E - June 2013
32E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 17 Status Indicators Link 1 status indicator Module status indicator Link 2 status indicator Network status indicator I/O status indicators Auxiliary power status indicator 45871 Publication 1732E-IN006C-EN-E - June 2013
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Indicator Status for Modules Indicator Status Description Module status Off No power applied to the device. Flashing red/green The module is performing POST (Power-On Self Test), which completes within 30 s. Green Device operating normally. Flashing red Module has experienced a recoverable fault. Red Unrecoverable fault – may require device replacement.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 19 Indicator Status for Modules Indicator Status I/O status Off The input or output channel is inactive, can be calibrated. Flashing Green Channel is calibrating. Green 1732E-IF4M12R – Normal operation, inputs being scanned. 1732E-OF4M12R – The output is active and under control. Flashing Red 1732E-IF4M12R – Fault. Channel is at end of range. 1732E-OF4M12R – Output fault.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules General Specifications Attributes Value Dimensions, approx., HxWxD 179 x 37 x 27 mm (7.05 x 1.46 x 1.06 in.) Weight, approx. 0.34 kg (0.75 lb) Wiring category(1) 1 – on signal ports 1 – on power ports 1 – on communication ports (1) Use this Conductor Category information for planning conductor routing. Refer to publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 21 Output Specifications – 1732E-OF4M12R Attributes Value Number of outputs 4 Resolution, min 16 bits Data format 16-bit sign magnitude Conversion rate < 2 ms Output type Configurable as voltage or current per channel Output range Current output Voltage output Short circuit protection, max Current output Voltage output 0…20 mA, 4…20 mA +/-10V, 10 mW 20 mA (0…20 mA mode) 20 mA per channel Accuracy 0.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules Environmental Specifications Attribute Value Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged Shock): 50 g Emissions CISPR 11: Group 1, Class A ESD immunity IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 10V/m with 1 kHz
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 23 Certifications Certification (when product is marked)(1) Value C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 EtherNet/IP ODVA conformance tested to EtherNet/IP specifications. (1) See the Product Certification link at http://www.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.