Manual
Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014 105
Appendix
C
Data Tables
Communicate with Your
Module
Read this section for information about how to communicate with your module.
I/O messages are sent to (consumed) and received from (produced) the
ArmorBlock I/O modules. These messages are mapped into the processor or
scanner memory. The following table lists the assembly instances and connection
points for the 1732E EtherNet/IP ArmorBlock Sequence of Events Input and
Scheduled Sourcing Output Modules.
Connection Points
In the following tables, Input pertains to the produced data from the module to
the controller, and Output refers to consumed data by the module from the
controller.
Catalog Number Connection Format Timestamp Module-Defined
Data Type
Assembly Instance /
Connection Point
(decimal)
1732E-IB8M8SOER Data (default) Per Point (default) Configuration 111
Input 157
Output 159
Data First In First Out Configuration 111
Input 158
Output 159
Data None Configuration 111
Input 104
Output 191
Listen Only None Configuration 189
Input 104
Output 191
1732E-OB8M8SR
(1)
Per Point Configuration 171
Input 177
Output 174
None Configuration 171
Input 191
Output 34
(1) There is no Listen Only connection for the 1732E-OB8M8SR because consumed assembly data is dependent on data in the produced assembly.